7 English
• Maintain a straight portion of 500 mm or more until the split of
the joint without wrapping any onsite piping around this area.
Over 500 mm of straight area can be maintained by connect-
ing at least 120 mm of onsite pipe (straight) to the joint.
(Refer to figure 18-3)
(Refer to figure 18)
1. Warning label
2. Horizontal surface
3. ±15° or less
4. Ground
5. Onsite pipe (120mm length or more)
6. Straight part of 500mm or more
7. FIELD WIRING
CAUTION
• All field wiring and components must be installed by a licensed
electrician and must comply with relevant local and national reg-
ulations.
• Be sure to use a dedicated power circuit. Never use a power sup-
ply shared by another appliance.
•
Never install a phase advancing capacitor. As this unit is equipped
with an inverter, installing a phase advancing capacitor will not only
deteriorate power factor improvement effect, but also may cause
capacitor abnormal heating accident due to high-frequency waves.
• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and
national regulations.
• This machine includes an inverter device. Connect earth and
leave charge to eliminate the impact on other devices by reducing
noise generated from the inverter device and to prevent leaked
current from being charged in the outer hull of the product.
• Do not connect the ground wire to gas pipes, sewage pipes, light-
ning rods, or telephone ground wires.
Gas pipes: can explode or catch fire if there is a gas leak.
Sewage pipes: no grounding effect is possible if hard plastic pip-
ing is used.
Telephone ground wires and lightning rods: dangerous when
struck by lightning due to abnormal rise in electrical potential in
the grounding.
• Be sure to install an earth leakage circuit breaker.
This unit uses an inverter, so install the earth leakage circuit
breaker that be capable of handling high harmonics in order to
prevent malfunctioning of the earth leakage circuit breaker itself.
• Earth leakage circuit breaker which are especially for protecting
ground-faults should be used in conjunction with main switch or
fuse for use with wiring.
Note
• Electrical wiring must be done in accordance with the wiring dia-
grams and the description herein.
• Do not operate until refrigerant piping work is completed.
(If operated before complete the piping work, the compressor may
be broken down.)
• Never remove thermistor, sensor or etc. when connecting power
wiring and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compres-
sor may be broken down.)
• This product have reversed phase protection detector that only
works when the power is turned on. If there exists black out or the
power goes on and off which the product is operating, attach a
reversed phase protection circuit locally. Running the product in
reversed phase may break the compressor and other parts.
• Attach the power wire securely. Introducing power with a missing
N-phase or with a mistaken N-phase will break the unit.
• Never connect the power supply in reversed phase.
The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.
• Make sure the electrical unbalance ratio is no greater than 2%. If
it is larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction
code will be displayed on the indoor remote controller.
• Connect the wire securely using designated wire and fix it with
attached clamp without applying external pressure on the termi-
nal parts (terminal for power wiring, terminal for transmission wir-
ing and earth terminal).
7-1 Power circuit, safety device, and cable
requirements
• A power circuit (see the following table) must be provided for con-
nection of the unit. This circuit must be protected with the required
safety devices, i.e. a main switch, a slow blow fuse on each phase
and an earth leakage circuit breaker.
• When using residual current operated circuit breakers, be sure to
use a high-speed type (1 second or less) 200mA rated residual
operating current.
• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with
relevant local and national regulations.
• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.
Use wire type H07RN-F when protected pipes are not used.
Note
The above table indicates power specifications for standard combi-
nations (see 2. INTRODUCTION).
7-2 Wiring Connection Example for Whole
System
(Refer to figure 19)
1. Power supply
2. Main switch
3. Earth leakage circuit breaker
4. Fuse
5. Outdoor unit
6. COOL/HEAT selector
7. Remote controller
8. Indoor unit
Note
• Make sure the weak electric wiring (i.e. for the remote control-
ler, between units, etc.) and the power wiring do not pass near
each other, keeping them at least 50 mm apart.
Proximity may cause electrical interference, malfunctions, and
breakage.
• Be sure to connect the power wiring to the power wiring termi-
nal block and secure it as described in “7-5 Power Wiring
Connection Procedure”.
•
Transmission wiring should be secured as described in “
7-4
Transmission Wiring Connection Procedure
”.
• Secure wiring with clamp such as insulation lock ties to avoid
contact with piping.
• Shape the wires to prevent the structure such as the EL.
COMPO. BOX lid deforming. And close the cover firmly.
7-3 Leading wire Procedure
• The power wiring and ground wiring are passed out from the
power wiring hole on the sides, the front (knock hole) or the bot-
tom frame (knock hole) .
• The transmission wiring is passed out from the wiring hole (knock
hole) on the front of the unit or from a piping hole.
Phase and
frequency
Voltage
Minimum
circuit amp.
Recom-
mended
fuses
RQYQ8PY1
φ 3, 50Hz 380-415V 18.5A 25A
RQYQ10PY1
φ 3, 50Hz 380-415V 21.6A 25A
RQYQ12PY1
φ 3, 50Hz 380-415V 22.7A 25A
RQYQ14PY1
φ 3, 50Hz 380-415V 31.5A 35A
RQYQ16PY1
φ 3, 50Hz 380-415V 31.5A 35A
RQYQ18PY1
φ 3, 50Hz 380-415V 32.5A 40A
RQYQ20PY1
φ 3, 50Hz 380-415V 41.2A 50A
RQYQ22PY1
φ 3, 50Hz 380-415V 44.3A 50A
RQYQ24PY1
φ 3, 50Hz 380-415V 50.0A 60A
RQYQ26PY1
φ 3, 50Hz 380-415V 51.0A 60A
RQYQ28PY1
φ 3, 50Hz 380-415V 54.1A 60A
RQYQ30PY1
φ 3, 50Hz 380-415V 55.2A 70A
RQYQ32PY1
φ 3, 50Hz 380-415V 63.0A 70A
RQYQ34PY1
φ 3, 50Hz 380-415V 64.0A 80A
RQYQ36PY1
φ 3, 50Hz 380-415V 65.0A 80A
RQYQ38PY1
φ 3, 50Hz 380-415V 73.7A 90A
RQYQ40PY1
φ 3, 50Hz 380-415V 81.5A 90A
RQYQ42PY1
φ 3, 50Hz 380-415V 82.5A 100A
RQYQ44PY1
φ 3, 50Hz 380-415V 83.5A 100A
RQYQ46PY1
φ 3, 50Hz 380-415V 86.6A 100A
RQYQ48PY1
φ 3, 50Hz 380-415V 87.7A 100A
Содержание
- Installation manual 1 1
- System air conditioner 1
- Ve upq series 1
- Figure 1 3
- Figure 10 figure 11 figure 12 figure 13 3
- Figure 14 3
- Figure 15 3
- Figure 2 3
- Figure 3 3
- Figure 4 3
- Figure 5 3
- Figure 6 3
- Figure 7 3
- Figure 8 3
- Figure 9 3
- Figure 16 4
- Figure 17 4
- Figure 18 4
- Figure 19 figure 20 4
- Figure 21 4
- Figure 22 4
- Figure 23 4
- Figure 24 4
- Figure 25 4
- Figure 26 4
- Figure 27 5
- Figure 28 5
- Figure 29 figure 30 5
- Figure 31 figure 32 5
- Figure 33 5
- Figure 34 5
- 1 safety precautions 6
- Contents 6
- English 6
- First of all 6
- Installation manual 6
- 1 combination 7
- 2 special notice of product 7
- 3 disposal requirements 7
- English 2 7
- Introduction 7
- 2 standard supplied accessories 8
- 3 option accessory 8
- 4 technical and electrical specifications 8
- 5 main components 8
- 6 installation process 8
- English 8
- Selection of location 8
- 1 selection of piping material and refrigerant branching kit 9
- English 4 9
- Inspecting and handling the unit 9
- Placing the unit 9
- Refrigerant piping 9
- 2 protection against contamination when installing pipes 10
- 3 pipe connection 10
- 4 connecting the refrigerant piping 10
- A b 25 10
- Cutting location 10
- English 10
- Gas side accessory pipe 2 10
- Gas side piping field supply 10
- Change as shown in the figure below rising height 200 mm or more 11
- Change to pattern 1 or pattern 2 11
- English 6 11
- Front connections 11
- If 2 m or more 11
- If less than 2m 11
- Less than 2m 11
- M or more 11
- Oil remains in the stopping outdoor unit 11
- Outdoor unit gas pipe 11
- Pattern 1 11
- Pattern 2 11
- Prohibited pattern 11
- To indoor unit 11
- Unit a 11
- Unit b 11
- 1 power circuit safety device and cable requirements 12
- 2 wiring connection example for whole system 12
- 3 leading wire procedure 12
- English 12
- Field wiring 12
- 4 transmission wiring connection procedure 13
- 5 power wiring connection procedure 13
- English 8 13
- Power wire crimp style terminal 13
- 1 preparations 14
- 2 air tight test and vacuum drying method 14
- 6 procedure for wiring inside units 14
- Air tight test and vacuum dry ing 14
- Air tight test and vacuum drying 14
- Crimp style terminal 14
- Cup washer 14
- Cut out section 14
- English 14
- R410a label 14
- Resin hook 14
- Terminal block crip style terminal wire narrow wire thick 14
- 1 before working 15
- Additional refrigerant charge and check operation 15
- Checking of device and instal lation conditions 15
- Checking of device and installation conditions 15
- English 10 15
- Pipe insulation 15
- 2 procedure of adding refrigerant charging and check operation 17
- English 12 17
- 1 before test run 18
- 1 onsite settings with the power off 18
- 2 onsite settings with the power on 18
- 2 test run 18
- 3 checks after test run 18
- Caution for refrigerant leaks 18
- English 18
- Onsite settings 18
- Test run 18
- English 14 19
Похожие устройства
- Daikin RQYQ14PY1 Инструкция по эксплуатации
- Daikin RQYQ14PY1 Сервис мануал
- Daikin RQYQ16PY1 Спецификация
- Daikin RQYQ16PY1 Руководство по вводу в эксплуатацию
- Daikin RQYQ16PY1 Инструкция по монтажу
- Daikin RQYQ16PY1 Инструкция по эксплуатации
- Daikin RQYQ16PY1 Сервис мануал
- Daikin RQYQ18PY1 Спецификация
- Daikin RQYQ18PY1 Руководство по вводу в эксплуатацию
- Daikin RQYQ18PY1 Инструкция по монтажу
- Daikin RQYQ18PY1 Инструкция по эксплуатации
- Daikin RQYQ18PY1 Сервис мануал
- Daikin RQYQ20PY1 Спецификация
- Daikin RQYQ20PY1 Руководство по вводу в эксплуатацию
- Daikin RQYQ20PY1 Инструкция по монтажу
- Daikin RQYQ20PY1 Инструкция по эксплуатации
- Daikin RQYQ20PY1 Сервис мануал
- Daikin RQYQ22PY1 Спецификация
- Daikin RQYQ22PY1 Руководство по вводу в эксплуатацию
- Daikin RQYQ22PY1 Сервис мануал