Daikin FXFA40A2VEB Технические данные онлайн

Daikin FXFA50A2VEB Технические данные онлайн
9
Indoor unit FXFA 20A 25A 32A 40A 50A 63A 80A 100A 125A
Cooling capacity
Total capacity
at high fan speed kW 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00
Heating capacity
Total capacity
at high fan speed kW 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00
Power input - 50Hz Cooling at high fan speed kW 0.04 0.05 0.06 0.09 0.12 0.19
Heating at high fan speed kW 0.04 0.05 0.06 0.09 0.12 0.19
Dimensions Unit HeightxWidthxDepth mm 204x840x840 246x840x840
288x840x840
Weight Unit kg 18 19 21 24 26
Casing Material Galvanised steel plate
Decoration panel Model
Standard panels: BYCQ140E - white with grey louvers / BYCQ140EW - full white / BYCQ140EB - black
Auto cleaning panels BYCQ140EGF - white / BYCQ140EGFB - black
Designer panels: BYCQ140EP - white / BYCQ140EPB - black
Dimensions HeightxWidthxDepth mm
Standard panels: 65x950x950 / Auto cleaning panels: 148x950x950 / Designer panels: 106x950x950
Weight kg
Standard panels: 5.5 / Auto cleaning panels: 10.3 / Designer panels: 6.5
Fan Air ow rate -
50Hz
Cooling At high fan speed /min 12.8 14.8 15.1 16.6 23.3 28.8 33.0
Heating At high fan speed /min 12.8 14.8 15.1 16.6 23.3 28.8 33.0
Air lter Type Resin net
Sound power level Cooling At high fan speed dBA 49 (4) 51 (4) 53 (4) 55 (4) 60 (4) 61 (4)
Sound pressure
level
Cooling L/ML/M/MH/H dBA 31/30/29/29.5/28 (4) 33 / 32 / 31 /30 / 29 (4) 35 / 34 / 33/32/30 (4) 38/ 36 /34 /32/30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4)
Heating L/ML/M/MH/H dBA 31/30/29/29.5/28 (4) 33 / 32/31 /30 /29 (4) 35 / 34 / 33 / 32/30 (4) 38/ 36 /34 /32 /30 (4) 43/41/37/34 /30 (4) 45/43/41/39 /36 (4)
Refrigerant Type/GWP R-32 / 675
Piping connections Liquid OD mm 6.35 9.52
Gas OD mm 9.52 12.7 15.9
Drain VP25 (O.D. 32 / I.D. 25)
Power supply Phase/Frequency/Voltage Hz/V 1~/50/60/220-240/220
Current - 50Hz Maximum fuse amps (MFA) (1) A 6
Control systems Infrared remote control BRC7FA532F (2)
Wired remote control BRC1H52W/S/K
() MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing
Round ow cassette
° air discharge for optimum eciency and comfort
Optimised design for R- refrigerant
Optional automatic lter cleaning results in higher eciency
& comfort and lower maintenance costs.
Two optional intelligent sensors improve energy eciency
and comfort
Widest choice ever in decoration panels: Designer, standard
and autocleaning panels in white (RAL) and black (RAL)
Bigger louvers and unique swing pattern improve equal
air distribution
Individual louver control: exibility to suit every room layout
without changing the location of the unit!
Lowest installation height in the market: mm for class -
Optional fresh air intake
Branch duct discharge allows to optimize air distribution in
irregular shaped rooms or to supply air to small adjacent rooms
Branch discharge Main discharge
Main unit
Standard drain pump with mm lift increases exibility
and installation speed
NEW
FXFA-A
BRPCBRCHW
Black design panel
White auto cleaning panel
Black panel
FXFA-A
White panel
Access all technical information on FXFA-A
at
my.daikin.eu or click here
NEW
() Must be combined with Madoka wired remote controller.
() L/ML/M/MH/H are the dierent fan speeds availble. L= low; ML= medium low; M= medium; MH= medium high; H= high
() Sound of designer panel: +dB