Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
User settings
└─ Preset values
└─ Room temperature
7.4.1.1 R/W [3-07]~[3-06], step: A.3.2.4
21°C
7.4.1.2 R/W [3-07]~[3-06], step: A.3.2.4
19°C
└─ LWT main
7.4.2.1 [8-09] R/W [9-01]~[9-00], step: 1°C
35°C
7.4.2.2 [8-0A] R/W [9-01]~[9-00], step: 1°C
33°C
7.4.2.5 R/W -10~10°C, step: 1°C
0°C
7.4.2.6 R/W -10~10°C, step: 1°C
-2°C
└─ Tank temperature
7.4.3.1 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
7.4.3.2 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
7.4.3.3 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
└─ Quiet level
7.4.4 R/W
0: Level 1 (*6)
1: Level 2 (*5)
2: Level 3
└─ Electricity price
7.4.5.1 [C-0C]
[D-0C]
R/W 0,00~990/kWh
0/kWh
7.4.5.2 [C-0D]
[D-0D]
R/W 0,00~990/kWh
0/kWh
7.4.5.3 [C-0E]
[D-0E]
R/W 0,00~990/kWh
0/kWh
└─ Fuel price
7.4.6 R/W 0,00~990/kWh
0,00~290/MBtu
8,0/kWh
└─ Set weather dependent
└─ Main
└────────────────── Set weather-dependent heating
7.7.1.1 [1-00] Set weather-dependent heating Low ambient temp. for LWT main zone heating
WD curve.
R/W -40~5°C, step: 1°C
-10°C
7.7.1.1 [1-01] Set weather-dependent heating High ambient temp. for LWT main zone heating
WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.1.1 [1-02] Set weather-dependent heating Leaving water value for low ambient temp. for
LWT main zone heating WD curve.
R/W
[9-01]~[9-00]°C, step: 1°C
35°C
7.7.1.1 [1-03] Set weather-dependent heating Leaving water value for high ambient temp. for
LWT main zone heating WD curve.
R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
└─ Additional
└────────────────── Set weather-dependent heating
7.7.2.1 [0-00] Set weather-dependent heating Leaving water value for high ambient temp. for
LWT add zone heating WD curve.
R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
7.7.2.1 [0-01] Set weather-dependent heating Leaving water value for low ambient temp. for
LWT add zone heating WD curve.
R/W [9-05]~[9-06]°C, step: 1°C
45°C
7.7.2.1 [0-02] Set weather-dependent heating High ambient temp. for LWT add zone heating
WD curve.
R/W 10~25°C, step: 1°C
15°C
7.7.2.1 [0-03] Set weather-dependent heating Low ambient temp. for LWT add zone heating
WD curve.
R/W -40~5°C, step: 1°C
-10°C
Installer settings
└─ System layout
└─ Standard
A.2.1.1 [E-00] R/O 0~5
0: LT s
p
lit
A.2.1.2 [E-01] R/O
0: 8 (*5)
1: 16
(
*6
)
A.2.1.3 [E-02] R/O
1: T
yp
e 2
A.2.1.4 [E-03] R/O
1: 1 ste
p
A.2.1.5 [5-0D] R/O
1: 1P,
(
1/1+2
)
A.2.1.6 [D-01] R/W
0: No
1: Open tariff
2: Closed tariff
3: Thermostat
A.2.1.7 [C-07] R/W 0: LWT control
1: Ext RT control
2: RT control
A.2.1.8 [7-02] R/W 0: 1 LWT zone
1: 2 LWT zones
A.2.1.9 [F-0D] R/W 0: Continuous
1: Sample
2: Re
q
ues
t
A.2.1.A [E-04] R/O
0: No (*6)
1: Yes
(
*5
)
A.2.1.B R/W 0: At unit
1: In room
└─ Options
A.2.2.1 [E-05] R/W
0: No
1: Yes
A.2.2.3 [E-07] R/O 0~6
1: T
yp
e 2
A.2.2.4 [C-05] R/W 1: Thermo ON/OFF
2: C/H re
q
ues
t
A.2.2.5 [C-06] R/W 1: Thermo ON/OFF
2: C/H re
q
ues
t
A.2.2.6.1 [C-02] Digital I/O PCB Ext. backup heat src R/W
0~3
0: No
1: Bivalent
A.2.2.6.2 [D-07] Digital I/O PCB Solar kit R/O
0~1
0: No
A.2.2.6.3 [C-09] Digital I/O PCB Alarm output R/W
0: Normally open
1: Normall
y
closed
A.2.2.6.4 [F-04] Digital I/O PCB Bottom plate heater R/W
0: No
1: Yes
A.2.2.7 [D-04] R/W
0: No
1: Pwr consm
p
ctrl
Forced off contact
Contact type add.
Demand PCB
Pump operation mode
Power saving possible
User interface location
DHW operation
DHW tank type
Contact type main
Indoor software type
Backup heater steps
BUH type
Unit control method
Number of LWT zones
High
Medium
Low
Unit type
Compressor type
Comfort (heating)
Eco (heating)
Storage comfort
Storage eco
Reheat
Field settings table
Installer setting at variance with
default value
Comfort (heating)
Eco (heating)
Comfort (heating)
Eco (heating)
(*5) *04/08*_
(*6) *16*
4P401673-1A - 2017.04
Содержание
- Field settings table 1
- Id66f2 1
- 5 04 08 _ 6 16 4p401673 1a 2017 4 3
- Field settings table 3
- Field settings table 4
- P401673 1a 2017 4 5 04 08 _ 6 16 4
- 5 04 08 _ 6 16 4p401673 1a 2017 4 5
- Field settings table 5
- Field settings table 6
- P401673 1a 2017 4 5 04 08 _ 6 16 6
- 5 04 08 _ 6 16 4p401673 1a 2017 4 7
- Field settings table 7
- Field settings table 8
- P401673 1a 2017 4 5 04 08 _ 6 16 8
Похожие устройства
- Daikin EHVZ16S18CB3V Приложение к руководству для дополнительного оборудования
- Daikin EHVZ16S18CB3V Инструкция по монтажу
- Daikin EHVZ16S18CB3V Таблица настроек полей
- Daikin EHVZ16S18CB3V Инструкция по эксплуатации
- Daikin EHBH04DA6V Технические данные
- Daikin EHBH04DA6V Инструкция по монтажу
- Daikin EHBH04DA6V Приложение к руководству для дополнительного оборудования
- MSI B450 GAMING PRO CARBON MAX WIFI Краткое Руководство
- Daikin EHBH04DA6V Руководство по монтажу
- Daikin EHBH04DA6V7 Технические данные
- Daikin EHBH04DA6V7 Инструкция по монтажу
- Daikin EHBH04DA6V Инструкция по эксплуатации
- Daikin EHBH04DA6V Руководство для установщика
- Daikin EHBH08DA6V7 Технические данные
- Daikin EHBH08DA6V7 Инструкция по монтажу
- Daikin EHBH04DA6V7 Приложение к руководству для дополнительного оборудования
- Daikin EHBH04DA6V Общие меры безопасности
- Daikin EHBH04DA6V7 Руководство по монтажу
- Daikin EHBH04DA6V Руководство по применению для пользователя
- Daikin EHBH08DA6V7 Приложение к руководству для дополнительного оборудования