Daikin FHY125BVE [6/16] Operation range

Daikin FH35BVE [6/16] Operation range
3 English
Neither place a flammable spray bottle near
the air conditioner nor perform spraying.
Doing so may result in a fire.
To clean the air conditioner, stop operation,
and unplug the power cord from the outlet.
Otherwise, an electric shock and injury may
result.
Do not operate the air conditioner with a wet
hand.
An electric shock may result.
Do not place items which might be damaged
by moisture under the indoor unit which may
be damaged by water.
Condensation may form if the humidity is above
80%, if the drain outlet gets blocked or the filter is
polluted.
Do not place a burner or heater at a place
directly exposed to the wind from the air con-
ditioner.
Incomplete combustion of the burner or heater
may result.
Do not allow a child to mount on the outdoor
unit or avoid placing any object on it.
Falling or tumbling may result in injury.
Never expose little children, plants or ani-
mals directly to the air flow.
Adverse influence to little children, animals and
plants may result.
Do not wash the air conditioner with water.
An electric shock or fire may result.
Do not install the air conditioner at any place
where flammable gas may leak out.
If the gas leaks out and stays around the air con-
ditioner, a fire may break out.
Execute complete drain piping for perfect
drainage.
Incomplete piping may result in a water leakage.
The appliance is not intended for use by
young children or infirm persons without
supervision.
Young children should be supervised to
ensure that they do not play with the appli-
ance.
Consult with installation contractor for
cleaning the inside of the air conditioner.
Wrong cleaning may make the plastics parts
broken or cause failure of water leakage or elec-
tric shock.
Do not touch the air inlet or aluminium fin of
the air conditioner.
Otherwise, injury may be caused.
Do not place objects in direct proximity of
the outdoor unit and do not let leaves and
other debris accumulate around the unit.
Leaves are a hotbed for small animals which can
enter the unit. Once in the unit, such animals can
cause malfunctions, smoke or fire when making
contact with electrical parts.
If the temperature or the humidity is beyond the fol-
lowing conditions, safety devices may work and the
air conditioner may not operate, or sometimes,
water may drop from the indoor unit.
COOLING ONLY TYPE
HEAT PUMP TYPE
3. OPERATION RANGE
OUTDOOR UNIT
TEMPERATURE [°C]
OUTDOOR INDOOR
R35
50
60GV1(A) 19.4 to 46 (DB)
21 to 32 (DB)/
14 to 23 (WB)
R71
100
125
FUV1/Y1
21 to 52 (DB)
21 to 35 (DB)/
14 to 25 (WB)
R50
60GVAL 19.4 to 54 (DB)
21 to 32 (DB)/
14 to 23 (WB)
R71
100
125
FUVAL/TAL
KUYAL
21 to 54 (DB)
21 to 35 (DB)/
14 to 25 (WB)
R71
100
125KUV1/Y1
21 to 46 (DB)
21 to 35 (DB)/
14 to 25 (WB)
R71
100
125KUVAL/TAL
21 to 46 (DB)
21 to 35 (DB)/
14 to 25 (WB)
OUTDOOR
UNIT
OPERA-
TION
TEMPERATURE
[°C]
OUTDOOR INDOOR
RY35FV1A
COOLING 19.4 to 46 (DB)
21 to 32 (DB)/
14 to 23 (WB)
HEATING
–9 to 21 (DB)/
–10 to 15.5 (WB)
15 to 28 (DB)
RY50
60GAV1A
COOLING 19.4 to 46 (DB)
21 to 32 (DB)/
14 to 23 (WB)
HEATING
–9 to 21 (DB)/
–10 to 15 (WB)
14 to 28 (DB)
RY71
100
125FUV1/Y1
COOLING –5 to 52 (DB)
21 to 35 (DB)/
14 to 25 (WB)
HEATING
–9 to 21 (DB)/
10 to 15.5 (WB)
15 to 27 (DB)
RY50
60GVAL
COOLING 19.4 to 54 (DB)
21 to 32 (DB)/
14 to 23 (WB)
HEATING
–9 to 21 (DB)/
–10 to 15 (WB)
14 to 28 (DB)
RY71
100
125FUVAL/TAL
COOLING –5 to 54 (DB)
21 to 35 (DB)/
14 to 25 (WB)
HEATING
–9 to 21 (DB)/
10 to 15.5 (WB)
15 to 24 (DB)
RY71
100
125
KUV1/Y1
COOLING –5 to 46 (DB)
21 to 35 (DB)/
12 to 25 (WB)
HEATING
–9 to 21 (DB)/
–10 to 15 (WB)
15 to 27 (DB)
01_EN_3P170549-4.fm Page 3 Friday, December 9, 2005 11:49 AM