Daikin FXUQ100AVEB9 [6/19] Specifications

Daikin FXUQ100AVEB9 [6/19] Specifications
Indoor Unit • 4-way blow ceiling suspended unit • FXUQ-A
1
2
VRV Systems • Indoor Unit
4
2 Specifications
Standard Accessories : Washer clamp;
Standard Accessories : Clamps;
Standard Accessories : Washer for hanger bracket;
Standard Accessories : Clamp metal;
Standard Accessories : Drain hose;
Standard Accessories : Declaration of conformity;
Standard Accessories : Installation manual;
Standard Accessories : Operation manual;
Notes
(1) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(2) Maximum allowable voltage range variation between phases is 2%.
(3) MCA/MFA: MCA = 1.25 x FLA
(4) MFA 4 x FLA
(5) Next lower standard fuse rating minimum 16A
(6) Select wire size based on the value of MCA
(7) Instead of a fuse, use a circuit breaker
2-2 Electrical Specifications FXUQ71A FXUQ100A
Power supply Phase 1~
Frequency Hz 50/60
Voltage V 220-240/220-230
Voltage range Min. % 10
Max. % 10
Current - 50Hz Minimum circuit amps (MCA) A 0.6 1.4
Maximum fuse amps (MFA) A 16
Full load amps
(FLA)
Fan motor A 0.5 1.1
Current - 60Hz Minimum circuit amps (MCA) A 0.6 1.4
Maximum fuse amps (MFA) A 16
Full load amps
(FLA)
Fan motor A 0.5 1.1