Its functioning relies on fluorinated greenhouse
gases
7. F-Gas Information
From 1/1/2015, a new F-Gas Regulation (EU) No 517/2014
comes into force repealing Regulation (EC) No 842/2006. This
will affect system labelling, information supplied within
documentation and also the way in which thresholds for frequen-
cy of leak testing.
For systems with a charge below 3kg, the changes to the leak
checking regime will not apply until 2017. Currently, there is no
requirement for regular leak testing of systems with a total
charge below 3kg.
Changes to leak testing requirements are as follows:
O-CU06-AUG17-3
All specifications are subjected to change by the manufacturer without prior notice. The English text is the original instruction.
Other languages are the translations of the original instructions.
10
This product is factory charged with N2.
The refrigerant system will be charged with fluorinated
greenhouse gases. Do not vent gases into the atmosphere.
The GWP (Global Warming Potential) values of refrigerants which
are specified for use in this equipment along with the three new
thresholds for leak testing requirements based on TCO2Eq (Tonnes
CO2 Equivalent) are as follows:
8. Trouble Shooting
This troubleshooting guide describes some common condensing unit
failure. Consult qualified personnel before any corrective actions are
taken.
OLD
LEGISLATION
NEW
LEGISLATION
LEAK CHECKING
FREQUENCY
Every 12 months but can be
increased to 24 months if
fitted with a fixed leak
detection system.
Every 6 months but can be
increased to 12 months if
fitted with a fixed leak
detection system.
Every 6 months however
automatic leak detection
system is mandatory which
requires servicing every
12 months.
550 TCO2Eq 330 kgs
50500
TCO2Eq
30300 kgs
500+ TCO2Eq 300+ kgs
Important information regarding the refrigerant used
Refrigerant Charge - kg
5T
CO
2
Eq
1.3
2.4
2.7
3.5
3.6
3.6
50T
CO
2
Eq
12.7
23.7
27.4
35.0
36.0
35.8
500T
CO
2
Eq
127
237
274
350
360
358
GWP
(1)
Refrigerant
R404A
R407A
R407F
R134a
R448A
R449A
3921.6
2107
1824.5
1430
1387
1397
Please fill in with indelible ink, on the refrigerant charge label
supplied with the product.
The total refrigerant charge & the TCO
2
equivalent for
charged refrigerant.
The filled out label must be adhered in the proximity of the
product charging port.
Failure Possible Causes
Fan does not work
Compressor does
not start
Insufficient cooling
Improper wiring
Improper wiring
System stopped because of
tripped of safety device.
Incorrect TXV size and SH
setting
Miss matching of indoor unit
Low refrigerant charge
Condenser coil dirty
Obstacle blocking
air inlet/outlet
Improper thermostat setting
Compressor rotating direction
is incorrect
Important Note
Warning! – Immediately shut off power of the unit if there is
any event of accident or breakdown.
Contains Fluorinated Greenhouse Gases
Charge
R404A
R407A
R407F
R448A
R449A
R134a
3922
2107
1825
1387
1397
1430
ENGLISH