14
Detailed description
[0] User permission level
If required, certain user interface buttons can be made unavailable for
the user.
Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons pfi and pfj immediately followed by
simultaneously pressing buttons s and ba, and keeping all 4
buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level – either level 2 or level 3 – is determined
by the field setting [0-00].
[1] Weather dependent set point
The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: low outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C.
■ Field settings for heating operation
■ [1-00] Low ambient temperature (Lo_A): low outdoor
temperature.
■ [1-01] High ambient temperature (Hi_A): high outdoor
temperature.
■ [1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
low outdoor temperatures (i.e. Lo_A) warmer water is
required.
■ [1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
■ Field settings for cooling operation
■ [1-05] Weather dependent for cooling function enable (1)/
disable (0)
■ [1-06] Low ambient temperature (Lo2_A): low outdoor
temperature.
■ [1-07] High ambient temperature (Hi2_A): high outdoor
temperature.
■ [1-08] Set point at low ambient temperature (Lo2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo2_A).
Note that the Lo2_Ti value should be higher than Hi2_Ti, as
for low outdoor temperatures (i.e. Lo2_A) less cold water
suffices.
■ [1-09] Set point at high ambient temperature (Hi2_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi2_A).
Note that the Hi2_Ti value should be lower than Lo2_Ti, as
for warmer outdoor temperatures (i.e. Hi2_A) colder water is
required.
T
t
Target water temperature
T
A
Ambient (outdoor) temperature
Shift value Shift value
Button
Permission level
1 2 3
Quiet mode button s operable — —
Weather dependent
set point button
ba operable — —
Schedule timer
enable/disable button
pr operable operable —
Programming button < operable — —
Time adjust buttons
pfi
pfj
operable — —
Inspection/test
operation button
z operable — —
Lo_Ti
Lo2_Ti
Lo_A
Lo2_A
Hi_A
Hi2_A
T
A
T
t
+ 05
00
– 05
Hi_Ti
Hi2_Ti
Shift value
Содержание
- Operation manual 1
- Unit for air to water heat pump system 1
- Definitions 2
- Efinitions 2
- Meaning of used terms 2
- Meaning of warnings and symbols 2
- Operation manual 2
- Afety precautions 3
- General safety precautions 3
- Introduction 3
- Ntroduction 3
- This manual 3
- This unit 3
- Features and functions 4
- Introduction 4
- Operating the digital controller 4
- Operating the unit 4
- Perating the unit 4
- Name and function of buttons and icons 5
- Setting the clock 6
- Setting the schedule timer 6
- Setting up the controller 6
- Description of the operation modes 7
- Domestic water heating operation 7
- Domestic water heating operation w 7
- Powerful domestic water heating operation 7
- Space cooling operation 7
- Space cooling operation c 7
- Space heating operation 7
- Space heating operation h 7
- Controller operations 8
- Manual operation 8
- Quiet mode operation 8
- Quiet mode operation s 8
- Schedule timer operation 9
- Getting started 10
- Programming and consulting the schedule timer 10
- Programming 11
- Consulting programmed actions 13
- Tips and tricks 13
- Field settings 14
- Ield settings 14
- Procedure 14
- Detailed description 15
- Field settings table 19
- Aintenance 21
- Disposal requirements 21
- Important information regarding the refrigerant used 21
- Isposal requirements 21
- Maintenance 21
- Maintenance activities 21
- Roubleshooting 21
- Standstill 21
- Troubleshooting 21
Похожие устройства
- Daikin EKCBX008BBV3 Инструкция по монтажу
- Daikin EKHWS150A 3V3 Инструкция по монтажу
- Daikin EKHWS200A 3V3 Инструкция по монтажу
- Daikin EKHWS300A 3V3 Инструкция по монтажу
- Daikin EKHWS200A 3Z2 Инструкция по монтажу
- Daikin EKHWS300A 3Z2 Инструкция по монтажу
- Daikin EKHWET150A3V3 Инструкция по монтажу
- Daikin EKHWS150B3V3 Инструкция по монтажу
- Daikin EKHWS200B3V3 Инструкция по монтажу
- Daikin EKHWS300B3V3 Инструкция по монтажу
- Daikin EKHWS200B3Z2 Инструкция по монтажу
- Daikin EKHWS300B3Z2 Инструкция по монтажу
- Daikin EKHWS150BA3V3 Инструкция по монтажу
- Daikin EKHWS200BA3V3 Инструкция по монтажу
- Daikin EKHWS300BA3V3 Инструкция по монтажу
- Daikin EKHWS200BA3Z2 Инструкция по монтажу
- Daikin EKHWS300BA3Z2 Инструкция по монтажу
- Asus DSL-AC68VG Краткое Руководство
- Asus DSL-AC88U Annex B Руководство Пользователя
- Asus DSL-AC88U Annex B Краткое Руководство