Daikin ERHQ016BAV3 [4/21] Specifications

Daikin ERHQ014BAV3 [4/21] Specifications
Heating Daikin Altherma
137
Daikin Altherma Low Temperature • Outdoor units • ERHQ006-016BAV3
2 Specifications
9
2
Piping connections Liquid (OD) Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 9,52 9,52 9,52 6,35 6,35 6,35
Gas Quantity 1 1 1
Type Flare connection
Diameter (OD) mm 15,9
Drain Quantity 3 3 3 1 1 1
Type Hole Hole Hole Socket Socket Socket
Diameter (OD) mm 26 26 26 18 18 18
Piping Length Minimum m 5 5 5 3 3 3
Maximum m 75 75 75 30 30 30
Equivalent m 95 95 95
Chargeless m 30 30 30
Additional Refrigerant Charge kg/m See installation
manual
outdoor unit
4PW37976-1B
See installation
manual
outdoor unit
4PW37976-1B
See installation
manual
outdoor unit
4PW37976-1B
0.02>10m 0.02>10m 0.02>10m
Installation height
difference
Maximum m 30 30 30
Max. internunit level difference m 20 20 20
Heat Insulation Both liquid and
gas pipes
Both liquid and
gas pipes
Both liquid and
gas pipes
Defrost Method Pressure
equalising
Pressure
equalising
Pressure
equalising
Reverse cycle Reverse cycle Reverse cycle
Defrost Control Sensor for outdoor heat exchanger temperature
Capacity Control Method Inverter controlled
Safety Devices Fan motor
thermal
protector
Fan motor
thermal
protector
Fan motor
thermal
protector
Fuse Fuse Fuse
High pressure
switch
High pressure
switch
High pressure
switch
2-2 TECHNICAL SPECIFICATIONS ERHQ011BAV3 ERHQ014BAV3 ERHQ016BAV3 ERHQ006BAV3 ERHQ007BAV3 ERHQ008BAV3