Daikin FTKS20DVMW9 [138/205] Indoor unit

Daikin FTXS35DVMW9 [138/205] Indoor unit
Indoor Unit SiEBE04-507
128 Removal Procedure
1. Indoor Unit
1.1 Removal of Air Filter
Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step Procedure Points
1. Appearance feature
Warning!
Dangerous: High voltage
A high voltage is applied to
all the electric circuits of this
product including
thermistors.
When a signal from the
remote controller is
received, the receiving tone
sounds and the operation
lamp flickers immediately to
confirm the signal reception.
When the ON/OFF switch is
kept pressed for 5 seconds,
the forced cooling operation
is performed for about 15
minutes.
2. Removing the air filter
1
2
3
Put your fingers on the
right and left projections
of the front panel, and
open the panel to the
position where it will
stop.
Slightly push up the
knob at the center of
the air filter and release
the hook.
Pull out the air filter
downwards and remove
it.
The air filter is not marked
for difference between the
right and left sides.
The air filter can be set
easily by inserting it along
the guides.
Insert the air filter with the
"FRONT"-marked face up.
Be sure to insert the hooks
(at 2 lower positions) when
mounting the air filter.
Operation lamp
TIMER lamp
INTELLIGENT EYE
(R4306)
(R4
305)
ON/OFF switch
(Test run switch)
Room temperature
thermistor
INTELLIGENT EYE
lamp
Signal receiver
(R4307)
(R4308)