Daikin FTKS25DVMW9 [51/205] Discharge pipe control

Daikin FTKS20DVML [51/205] Discharge pipe control
SiEBE04-507 Control Specification
Function and Control 41
3.3.4 3-minutes Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
3.4 Discharge Pipe Control
Outline The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
88
64
48
240
360
180
Frequency
TCG1sec TCG2sec TCG3sec
Time
(R2949)
FCG3
FCG2
FCG1
Zone Control contents
Stop zone When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone Start the timer, and the frequency will be drooping.
Keep zone Keep the upper limit of frequency.
Return / Reset zone Cancel the upper limit of frequency.
105°C
101°C
99°C
Stop zone 110°C
Drooping zone
Keep zone
Up zone
(R4270)
Heat exchanger
thermistor
temperature
Reset zone 97°C