11 ■English
Test Run and Final Check
1.
Trial Operation and Testing
1-1 Measure the supply voltage and make sure that it falls in the specified range.
1-2 Trial operation should be carried out in either cooling or heating mode.
■ For Heat pump
• In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temper-
ature.
1) Trial operation may be disabled in either mode depending on the room temperature.
2) After trial operation is complete, set the temperature to a normal level (26°C to 28°C in cooling mode, 20°C to 24°C in
heating mode).
3) For protection, the system disables restart operation for 3 minutes after it is turned off.
■ For Cooling only
• Select the lowest programmable temperature.
1) Trial operation in cooling mode may be disabled depending on the room temperature.
Use the remote control for trial operation as described below.
2) After trial operation is complete, set the temperature to a normal level (26°C to 28°C ).
3) For protection, the unit disables restart operation for 3 minutes after it is turned off.
1-3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts,
such as louver movement, are working properly.
• The air conditioner requires a small amount of power in its standby mode. If the system is not to be used for some
time after installation, shut off the circuit breaker to eliminate unnecessary power consumption.
• If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation
mode when the circuit breaker is opened again.
2.
Test Items
Test Items
Symptom
(diagnostic display on RC)
Check
Indoor and outdoor units are installed properly on solid bases. Fall, vibration, noise
No refrigerant gas leaks. Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated. Water leakage
Draining line is properly installed. Water leakage
System is properly earthed. Electrical leakage
The specified wires are used for interconnecting wire connections. Inoperative or burn damage
Indoor or outdoor unit’s air intake or exhaust has clear path of air.
Shut-off valves are opened.
Incomplete cooling/heating function
Indoor unit properly receives remote control commands. Inoperative
01_EN_3P119321-7W.fm Page 11 Thursday, March 8, 2007 6:23 PM
Содержание
- Arxg25cvmb arxg25e2v1b arxg35cvmb arxg35e2v1b 1
- Arxs20c2vmb arks20c2vmb arxs25c2vmb arks25c2vmb arxs35c2vmb arks35c2vmb 1
- Arxs20cvmb arks20cvmb arxs25cvmb arks25cvmb arxs35cvmb arks35cvmb 1
- Installation manual 1
- Models rxs20cvmb rks20cvmb rxs25cvmb rks25cvmb rxs35cvmb rks35cvmb 1
- R410a split series 1
- Rxg25cvmb rxg25e2v1b rxg35cvmb rxg35e2v1b 1
- Rxs20c2vmb rks20c2vmb rxs25c2vmb rks25c2vmb rxs35c2vmb rks35c2vmb 1
- Daikin industries ltd 2
- Noboru murata manager quality control department shiga 1st of nov 2005 2
- Rxs20cvmb rxs25cvmb rxs35cvmb rks20cvmb rks25cvmb rks35cvmb arxs20cvmb arxs25cvmb arxs35cvmb arks20cvmb arks25cvmb arks35cvmb rxg25cvmb rxg35cvmb arxg25cvmb arxg35cvmb rxs20cvmb9 rxs25cvmb9 rxs35cvmb9 rks20cvmb9 rks25cvmb9 rks35cvmb9 arxs20cvmb9 arxs25cvmb9 arxs35cvmb9 arks20cvmb9 arks25cvmb9 arks35cvmb9 rxg25cvmb9 rxg35cvmb9 arxg25cvmb9 arxg35cvmb9 rxs20c2vmb rxs25c2vmb rxs35c2vmb rks20c2vmb rks25c2vmb rks35c2vmb arxs20c2vmb arxs25c2vmb arxs35c2vmb arks20c2vmb arks25c2vmb arks35c2vmb rxg25e2v1b rxg35e2v1b arxg25e2v1b arxg35e2v1b 2
- Sb63475 4c 2
- Umeda center bldg 4 12 nakazaki nishi 2 chome kita ku osaka 530 8323 japan 2
- Caution 3
- English 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- English 2 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- Outdoor unit installation drawings 5
- Drain work heat pump models 6
- English 4 6
- Installation guidelines 6
- Installing outdoor unit 6
- Outdoor unit installation 6
- Precautions on installation 6
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- English 6 8
- Purging air and checking gas leakage 8
- Warning 8
- Gas pipe thermal insulation 9
- Important information regarding the refrigerant used 9
- O d 6 mm 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- The filled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover 9
- When using commercial copper pipes and fittings observe the following 9
- _en_3p119321 7w fm page 7 thursday march 8 2007 6 23 pm 9
- Caution 10
- English 8 10
- Facility setting cooling at low outdoor temperature 10
- How to force cooling operation mode 10
- Pump down operation 10
- English 11
- Firmly secure wire retainer so wire terminations will not receive external stress 11
- Power supply terminal block 11
- Shape wires so that the service lid fit securely 11
- Use the specified wire type and connect it securely 11
- Warning 11
- Wiring 11
- Caution 12
- English 10 12
- English 13
- Test items 13
- Test run and final check 13
- Trial operation and testing 13
- P119321 7w m05b063d 14
Похожие устройства
- Daikin RXS25C2VMB Сервис мануал
- Daikin RXS35C2VMB Инструкция по монтажу
- Daikin RXS35C2VMB Сервис мануал
- Daikin RKS20C2VMB Инструкция по монтажу
- Daikin RKS20C2VMB Сервис мануал
- Daikin RKS25C2VMB Инструкция по монтажу
- Daikin RKS25C2VMB Сервис мануал
- Daikin RKS35C2VMB Инструкция по монтажу
- Daikin RKS35C2VMB Сервис мануал
- Daikin ARXS20C2VMB Инструкция по монтажу
- Daikin ARXS25C2VMB Инструкция по монтажу
- Daikin ARXS35C2VMB Инструкция по монтажу
- Daikin ARKS20C2VMB Инструкция по монтажу
- Daikin ARKS25C2VMB Инструкция по монтажу
- Daikin ARKS35C2VMB Инструкция по монтажу
- Daikin RXG25CVMB Технические данные
- Daikin RXG25CVMB Инструкция по монтажу
- Daikin RXG35CVMB Технические данные
- Daikin RXG35CVMB Инструкция по монтажу
- Daikin RXG25E2V1B Технические данные