SiBE12-816_C Code Indication on Remote Controller
Service Diagnosis 192
4. Code Indication on Remote Controller
4.1 RA Indoor Unit - F(C)TXG, FTXS, FVXS, FLK(X)S,
FDK(X)S Series
4.2 SA Indoor Unit - FFQ Series
: Error code displays automatically and system stops.
Inspect and repair it.
: In the case of the shaded error codes, “inspection” is not displayed. The system
operates, but be sure to inspect and repair it.
Note: There is a possibility of open phase power supply, also check power supply.
Error Codes Description Reference Page
00
Normal condition
A1
Indoor unit PCB abnormality 194
A5
Freeze-up protection control or heating peak-cut control 195
A6
Fan motor or related abnormality
AC motor (duct, floor / ceiling) 197
DC motor (wall, floor standing) 198
C4
Indoor heat exchanger thermistor or related abnormality 200
C9
Room temperature thermistor or related abnormality 200
Error Codes Description Remarks Reference Page
A1
Indoor unit PCB abnormality 201
A3
Drain water level system
abnormality
202
A6
Fan motor or related abnormality (See Note.) 204
AF
Drain system abnormality
Activation of float switch
during compressor off.
205
C4
Thermistor or related abnormality 206
C9
Thermistor or related abnormality 206
CJ
Remote controller air thermistor
abnormality
Failure of remote controller air
thermistor.
Unit can be operated by
indoor unit thermistor.
208