■English 6
5.
Purging air and checking gas leakage.
• When piping work is completed, it is necessary to purge the air and check for gas leakage.
WARNING
1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum
pump or the unit.
• If using additional refrigerant, perform air purging from the refrigerant pipes and
indoor unit using a vacuum pump, then charge additional refrigerant.
• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified
tightening torque.
*1. Pipe length vs. vacuum pump run time.
*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.
Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).
1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.
2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).
(High-pressure valve subsequently requires no operation.)
3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg)*1.
4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.
(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.
5) Remove caps from liquid stop valve and gas stop valve.
6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.
7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.
(Do not attempt to turn valve rod beyond its stop.)
8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.
Pipe length Up to 15 metres
Run time Not less than 10 min.
Compound
pressure gauge
Pressure
meter
High-
pressure
valve
Low-pressure
valve
Vacuum pump
Service port
Liquid
stop
valve
Valve caps
Gas stop valve
Charging
hoses
Gauge
manifold
01_EN_3P207974-2D.fm Page 6 Friday, September 4, 2009 1:45 PM
Содержание
- Arx20gv1b arx25gv1b arx35gv1b arx20jv1b arx25jv1b arx35jv1b 1
- Installation manual 1
- Models 1
- R410a split series 1
- Umeda center bldg 2 4 12 nakazaki nishi kita ku osaka 530 8323 japan 2
- Caution 3
- English 3
- Safety precautions 3
- Warning 3
- Accessories 4
- Accessories supplied with the outdoor unit 4
- Caution 4
- English 2 4
- Precautions for selecting the location 4
- Caution 5
- English 5
- Outdoor unit installation drawings 5
- Drain work heat pump models 6
- English 4 6
- Installation guidelines 6
- Installing outdoor unit 6
- Outdoor unit installation 6
- Precautions on installation 6
- Caution 7
- Flaring the pipe end 7
- Outdoor unit installation 7
- Refrigerant piping 7
- Warning 7
- English 6 8
- Purging air and checking gas leakage 8
- Warning 8
- Important information regarding the refrigerant used 9
- Outdoor unit installation 9
- Refilling the refrigerant 9
- Refrigerant piping work 9
- Caution 10
- English 8 10
- How to force cooling operation mode 10
- Pump down operation 10
- English 11
- Firmly secure wire retainer so wire terminations will not receive external stress 11
- Power supply terminal block 11
- Shape wires so that the stop valve cover fit securely 11
- Use the specified wire type and connect it securely 11
- Warning 11
- Wiring 11
- Caution 12
- English 10 12
- Good wrong 12
- English 13
- Test items 13
- Test run and final check 13
- Trial operation and testing 13
- P207974 2d m07b064c 14
Похожие устройства
- Daikin ARX35GV1B Сервис мануал
- Daikin FTK20GV1B Технические данные
- Daikin FTK20GV1B Сервис мануал
- Daikin FTK25GV1B Технические данные
- Daikin FTK25GV1B Сервис мануал
- Daikin FTK35GV1B Технические данные
- Daikin FTK35GV1B Сервис мануал
- Daikin RKS20G2V1B Инструкция по монтажу
- Daikin RKS20G2V1B Технические данные
- Daikin RKS20G2V1B Сервис мануал
- Daikin RKS25G2V1B Инструкция по монтажу
- Daikin RKS25G2V1B Технические данные
- Daikin RKS25G2V1B Сервис мануал
- Daikin RKS35G2V1B Инструкция по монтажу
- Daikin RKS35G2V1B Технические данные
- Daikin RKS35G2V1B Сервис мануал
- Daikin RKS42G2V1B Инструкция по монтажу
- Daikin RKS42G2V1B Технические данные
- Daikin RKS42G2V1B Сервис мануал
- Daikin RKS50G2V1B Технические данные