Daikin FTKS50FVLT [137/244] Insufficient gas

Daikin FTKS71FVM [137/244] Insufficient gas
Troubleshooting Si04-703A
126 Service Diagnosis
4.22 Insufficient Gas
Remote
Controller
Display
U0
Method of
Malfunction
Detection
Gas shortage detection I :
A gas shortage is detected by checking the CT-detected input current value and the compressor
running frequency.
Gas shortage detection II :
A gas shortage is detected by checking the difference between indoor unit heat exchanger
temperature and room temperature as well as the difference between outdoor unit heat
exchanger temperature and room temperature.
Malfunction
Decision
Conditions
Gas shortage detection I :
DC current
(A/Hz) × Output frequency +
However, when the status of running frequency > 55 (Hz) is kept on for a certain time.
Note : The values are different from model to model.
Gas shortage detection II :
If a gas shortage error takes place 4 times successively, the system will be shut down. The error
counter will reset itself if this or any other error does not occur during the following 60-minute
compressor running time (total time).
Supposed
Causes
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Discharge pipe thermistor disconnected, or indoor unit or outdoor unit heat exchanger
thermistor disconnected, room or outside air temperature thermistor disconnected
Stop valve closed
Electronic expansion valve defective
50/60 class 18 / 1000 0.7
71 FVM(T) 27 / 1000 2.5
71 FVMA 27 / 1000 2.0