Daikin RXS60FVMA [118/244] Check no 7 refer to p 33

Daikin RXS71FVMA [118/244] Check no 7 refer to p 33
Si04-703A Troubleshooting
Service Diagnosis 107
Troubleshooting
Check No.07
Refer to P.133
Check No.08
Refer to P.134
Check No.14
Refer to P.137
(R8064)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
An input over-current may result from wrong internal wiring. If the wires have been disconnected and
reconnected for part replacement, for example, and the system is interrupted by an input over-current,
check the wires again.
NO
YES
NO
YES
YES
NO
Get restarted and measure the
input current.
Check No. 14
Check the main circuit electrolytic
capacitor.
Check No. 08
Check the discharge pressure.
Check No. 07
Check the installation condition.
Check with the inverter checker ().
Turn off the power and disconnect
the harnesses U, V and W.
Turn off the power, and reconnect
the harnesses. Turn on the power
again and get restarted.
Replace the outdoor unit
PCB.
Replace the electrolytic
capacitor.
Correct the power supply or
replace the PM1.
(Replace the outdoor unit
PCB.)
Normal?
Any LED off?
Input current flowing
above its stop level?
Inverter checker
Part No.: 1225477