Cooling Only SiBE12-314
12 Specifications
1.2 Outdoor Units
230V, 50Hz
Notes:
1.
See “Combination Capacity”.
2. The data are based on the conditions shows in the table below.
Combination Capacity
Cooling [230V]
50Hz
Note:
Cooling capacity is based on 27°CDB/19°CWB (Indoor temperature), 35°CDB (Outdoor temperature).
3D040485#1
Model
2MKS40BVMB 2AMKS40BVMB
Cooling Capacity
kW
Power Consumption
W—
Running Current
A—
Casing Color Ivory White
Compressor
Type Hermetically Sealed Swing Type
Model 1YC23GXD
Motor Output W 600
Refrigerant
Oil
Model FVC50K
Charge L 0.40
Refrigerant
Type R410A
Charge kg 0.98
Air Flow Rate
m³/min
HH 39
H35
L30
cfm
HH 1126
H 1010
L 866
Fan
Type Propeller
Motor Output W 50
Starting Current A 5.6
Dimension (H
×
W
×
D) mm 640
×
685
×
285
Packaged Dimension (W
×
D
×
H) mm 800
×
366
×
676
Weight kg 39
Gross Weight kg 42
Operation
Sound
Sound pressure dBA 47
Silent Mode dBA 43
Sound Power dBA 62
Piping
Connection
Liquid mm
φ
6.4
×
2
Gas mm
φ
9.5
×
2
Drain mm
φ
18
Heat Insulation Both Liquid & Gas Pipes
No. of Wiring Connection 3 for Power Supply, 4 for Interunit Wiring
Max. Piping Length m
30 (for Total of Each Room)
20 (for One Room)
Min. Piping Length m 1.5 (for One Room)
Amount of Additional Charge g/m 20 (20m or more)
Max. Installation Height Difference m
15 (between Indoor Unit and Outdoor Unit)
7.5 (between Indoor Units)
Drawing No. 3D040484 3D040485
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3414
cfm=m³/mi35.3
Cooling Piping Length
Indoor ; 27°CDB/19°CWB
Outdoor ; 35°CDB
7.5m
Combination of
Indoor Unit
Each Capacity (kW) Total Capacity (kW) Total Input (W) Total Current (A)
Power factor
(%)
A room B room Rating (min~max) Rating (min~max) Rating (min~max) Rating
2.5
2.50 2.50 1.20~3.00 755 340~1020 3.5 1.9~4.7 94
3.5
3.15 3.15 1.20~3.60 1120 340~1440 5.1 1.9~6.5 95
2.5+2.5
1.95 1.95 3.90 1.50~4.20 1215 400~1490 5.6 2.2~6.8 94
2.5+3.5
1.75 2.15 3.90 1.50~4.20 1215 400~1490 5.6 2.2~6.8 94