2 | General safety precautions
Installer reference guide
11
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 split series
4P518023-11H – 2021.03
2.1.3 Refrigerant — in case of R410A or R32
If applicable. See the installation manual or installer reference guide of your
application for more information.
NOTICE
Make sure refrigerant piping installation complies with applicable legislation. In
Europe, EN378 is the applicable standard.
NOTICE
Make sure the field piping and connections are NOT subjected to stress.
WARNING
During tests, NEVER pressurize the product with a pressure higher than the
maximum allowable pressure (as indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks,
ventilate the area immediately. Possible risks:
▪ Excessive refrigerant concentrations in a closed room can lead to oxygen
deficiency.
▪ Toxic gas might be produced if refrigerant gas comes into contact with fire.
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
▪ Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
▪ Use a separate recovery system so that the unit's compressor does NOT have to
operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them directly into the environment.
Use a vacuum pump to evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is no gas leak. Use nitrogen
to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more than the specified amount
of refrigerant.
▪ When the refrigerant system is to be opened, refrigerant MUST be treated
according to the applicable legislation.
Содержание
- Installer reference guide 1
- R32 split series 1
- About the box 21 2
- About the documentation 4 2
- About the unit 23 2
- Charging refrigerant 42 2
- General safety precautions 7 2
- Installer reference guide 2
- Piping installation 32 2
- Specific installer safety instructions 15 2
- Table of contents 2
- Unit installation 24 2
- Commissioning 53 3
- Configuration 52 3
- Disposal 61 3
- Electrical installation 46 3
- Finishing the outdoor unit installation 51 3
- Glossary 67 3
- Hand over to the user 56 3
- Maintenance and service 57 3
- Table of contents 3
- Technical data 63 3
- Troubleshooting 59 3
- About the documentation 4
- About this document 4
- About the documentation 5
- Meaning of warnings and symbols 5
- About the documentation 6
- For the installer 7
- General 7
- General safety precautions 7
- General safety precautions 8
- Installation site 8
- Caution 9
- Determine the total refrigerant charge in the system factory refrigerant charge additional refrigerant amount charged 9
- General safety precautions 9
- Installation space requirements 9
- Notice 9
- To determine the minimum floor area 9
- Warning 9
- 1 m floor standing units 10
- 2 m ceiling mounted units 10
- Ceiling mounted unit 10
- Determine which graph or table to use 10
- For indoor units is the unit ceiling mounted wall mounted or floor 10
- For outdoor units installed or stored indoors this depends on the installation 10
- General safety precautions 10
- Height 10
- If the installation height is then use the graph or table for 10
- Installer reference guide 10
- P518023 11h 2021 3 10
- R32 split series 10
- Rxtm r_rxtp r_arxtp r_rxta b 10
- Standing 10
- Use the graph or table to determine the minimum floor area 10
- Wall mounted unit 10
- X 2 m wall mounted units 10
- Danger risk of explosion 11
- General safety precautions 11
- If applicable see the installation manual or installer reference guide of your application for more information 11
- Notice 11
- Refrigerant in case of r410a or r32 11
- Warning 11
- Electrical 12
- General safety precautions 12
- Caution 13
- General safety precautions 13
- Notice 13
- Warning 13
- General safety precautions 14
- Notice 14
- Warning 14
- Specific installer safety instructions 15
- Caution 16
- Danger risk of explosion 16
- Specific installer safety instructions 16
- Warning 16
- Caution 17
- Charging refrigerant see 8 charging refrigerant 4 42 17
- Electrical installation see 9 electrical installation 4 46 17
- Specific installer safety instructions 17
- Warning 17
- Specific installer safety instructions 18
- Specific installer safety instructions 19
- Specific installer safety instructions 20
- About the box 21
- Outdoor unit 21
- Overview about the box 21
- To handle the outdoor unit 21
- To unpack the outdoor unit 21
- About the box 22
- If the aluminum fins on the unit are bent straighten them with a fin comb field supply 22
- Lift the outdoor unit 22
- Make sure the unit is placed on a flat surface to avoid damage 22
- Only handle the outdoor unit as follows 22
- Remove the accessories at the bottom of the package 22
- To remove the accessories from the outdoor unit 22
- About the unit 23
- Identification 23
- Identification label outdoor unit 23
- In this chapter 24
- Preparing the installation site 24
- Unit installation 24
- Installation site requirements of the outdoor unit 25
- Unit installation 25
- Unit installation 26
- Additional installation site requirements of the outdoor unit in cold climates 27
- Unit installation 27
- About mounting the outdoor unit 28
- About opening the unit 28
- Mounting the outdoor unit 28
- Opening the unit 28
- To open the outdoor unit 28
- Unit installation 28
- Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise 29
- Fix the unit securely by means of foundation bolts in accordance with the foundation drawing 29
- Information 29
- Precautions when mounting the outdoor unit 29
- Prepare 4 sets of m8 or m10 anchor bolts nuts and washers field supply 29
- To provide the installation structure 29
- Unit installation 29
- Use a vibration proof rubber field supply in cases where vibrations may be transmitted to the building 29
- To install the outdoor unit 30
- To prevent the outdoor unit from falling over 30
- To provide drainage 30
- Unit installation 30
- Unit installation 31
- In this chapter 32
- Piping installation 32
- Preparing refrigerant piping 32
- Refrigerant piping requirements 32
- About connecting the refrigerant piping 33
- Connecting the refrigerant piping 33
- Piping installation 33
- Refrigerant piping insulation 33
- Refrigerant piping length and height difference 33
- Piping installation 34
- Precautions when connecting the refrigerant piping 34
- Guidelines when connecting the refrigerant piping 35
- Piping installation 35
- Pipe bending guidelines 36
- Piping installation 36
- To flare the pipe end 36
- Using the stop valve and service port 36
- Piping installation 37
- About checking the refrigerant piping 38
- Checking the refrigerant piping 38
- Piping installation 38
- To connect the refrigerant piping to the outdoor unit 38
- Piping installation 39
- Precautions when checking the refrigerant piping 39
- To check for leaks 39
- Piping installation 40
- To perform vacuum drying 40
- After opening the stop valve it is possible that the pressure in the refrigerant piping does not increase this might be caused by e g the closed state of the expansion valve in the outdoor unit circuit but does not present any problem for correct operation of the unit 41
- Information 41
- Piping installation 41
- About charging refrigerant 42
- Charging refrigerant 42
- In this chapter 42
- About the refrigerant 43
- Charging refrigerant 43
- Charging refrigerant 44
- Precautions when charging refrigerant 44
- To charge additional refrigerant 44
- To determine the additional refrigerant amount 44
- To determine the complete recharge amount 44
- Charging refrigerant 45
- To fix the fluorinated greenhouse gases label 45
- About connecting the electrical wiring 46
- Electrical installation 46
- In this chapter 46
- Precautions when connecting the electrical wiring 46
- Danger risk of electrocution 47
- Electrical installation 47
- Warning 47
- A curled single core wire 48
- B screw 48
- C flat washer 48
- Electrical installation 48
- End of the wire place the round crimp style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool 48
- Guidelines when connecting the electrical wiring 48
- If stranded conductor wires are used install a round crimp style terminal on the 48
- Keep the following in mind 48
- Single core wire 48
- Use the following methods for installing wires 48
- Wire type installation method 48
- Electrical installation 49
- Specifications of standard wiring components 49
- To connect the electrical wiring to the outdoor unit 49
- Connect the interconnection cable and power supply as follows 50
- Electrical installation 50
- Open the wire clamp 50
- Tighten the terminal screws securely we recommend using a phillips screwdriver 50
- Closing the unit 51
- Finishing the outdoor unit installation 51
- To close the outdoor unit 51
- To finish the outdoor unit installation 51
- Configuration 52
- Facility setting 52
- To set the facility mode 52
- Commissioning 53
- In this chapter 53
- Overview commissioning 53
- Precautions when commissioning 53
- After the installation of the unit first check the items listed below once all checks are fulfilled the unit must be closed power up the unit after it is closed 54
- Checklist before commissioning 54
- Checklist during commissioning 54
- Commissioning 54
- During test operation the outdoor unit and the indoor units will start up make sure that the preparations of all indoor units are finished field piping electrical wiring air purge see installation manual of the indoor units for details 54
- Information 54
- Prerequisite power supply must be in the specified range 54
- Prerequisite test run may be performed in cooling or heating mode 54
- To perform a test run 54
- Commissioning 55
- Starting up the outdoor unit 55
- Hand over to the user 56
- Maintenance and service 57
- Maintenance safety precautions 57
- Overview maintenance and service 57
- About the compressor 58
- Checklist for yearly maintenance of the outdoor unit 58
- Maintenance and service 58
- Winter season 58
- Overview troubleshooting 59
- Precautions when troubleshooting 59
- Solving problems based on symptoms 59
- Symptom indoor units fall vibrate or make noise 59
- Troubleshooting 59
- Fault diagnosis using led on outdoor unit pcb 60
- Symptom electrical leakage 60
- Symptom the unit is not heating or cooling as expected 60
- Symptom unit does not function or burn damage 60
- Symptom water leakage 60
- Troubleshooting 60
- Disposal 61
- Overview disposal 61
- To pump down 61
- Disposal 62
- To start and stop forced cooling 62
- To start and stop forced cooling using the indoor unit on off switch 62
- To start and stop forced cooling using the indoor unit user interface 62
- Technical data 63
- Unified wiring diagram legend 63
- Wiring diagram 63
- Technical data 64
- Technical data 65
- Ped categories of equipment high pressure switch category iv compressor category ii other equipment art 4 3 66
- Piping diagram 66
- Piping diagram outdoor unit 66
- Technical data 66
- Glossary 67
Похожие устройства
- Daikin ARXTP35R2V1B Руководство по монтажу
- Daikin ARXTP35R2V1B Инструкция по монтажу
- Daikin RXTA30B2V1B Руководство по монтажу
- Daikin RXTA30B2V1B Инструкция по монтажу
- Daikin RXTP25R2V1B Руководство по монтажу
- Daikin RXTP25R2V1B Инструкция по монтажу
- Daikin RXTP35R2V1B Руководство по монтажу
- Daikin RXTP35R2V1B Инструкция по монтажу
- Daikin FTV25AV1 Инструкция по монтажу
- Daikin FTV35AV1 Инструкция по монтажу
- Daikin FTV50AV1 Инструкция по монтажу
- Daikin FTV60AV1 Инструкция по монтажу
- Daikin RV25AV1 Инструкция по монтажу
- Daikin RV35AV1 Инструкция по монтажу
- Daikin RV50AV1 Инструкция по монтажу
- Daikin RV60AV1 Инструкция по монтажу
- Gorenje B2470E Руководство по эксплуатации
- Prology CMX-230 Инструкция по эксплуатация
- Prology CMX-230 Краткое руководство пользователя
- Prology CMX-240 Инструкция по эксплуатация