2 Specific installer safety instructions
Installation manual
6
RXTM-R_RXTP-R_ARXTP-R_RXTA-B
R32 split series
3P482320-14U – 2021.03
WARNING
▪ If the power supply has a missing or wrong N-phase,
equipment might break down.
▪ Establish proper earthing. Do NOT earth the unit to a
utility pipe, surge absorber, or telephone earth.
Incomplete earthing may cause electrical shock.
▪ Install the required fuses or circuit breakers.
▪ Secure the electrical wiring with cable ties so that the
cables do NOT come in contact with sharp edges or
piping, particularly on the high-pressure side.
▪ Do NOT use taped wires, stranded conductor wires,
extension cords, or connections from a star system.
They can cause overheating, electrical shock or fire.
▪ Do NOT install a phase advancing capacitor, because
this unit is equipped with an inverter. A phase
advancing capacitor will reduce performance and may
cause accidents.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
Use an all-pole disconnection type breaker with at least
3 mm between the contact point gaps that provide full
disconnection under overvoltage category III.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
WARNING
Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.
WARNING
▪ Do NOT use locally purchased electrical parts inside
the product.
▪ Do NOT branch the power supply for the drain pump,
etc. from the terminal block. This could result in
electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes
without thermal insulation as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by
the power supply. Do not touch them with bare hands.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing. The
voltage MUST be less than 50VDC before you can touch
electrical components. For the location of the terminals,
see the wiring diagram.
Finishing indoor unit installation (see "8Finishing the outdoor
unit installation"[412])
DANGER: RISK OF ELECTROCUTION
▪ Make sure that the system is earthed properly.
▪ Turn off the power supply before servicing.
▪ Install the switch box cover before turning on the power
supply.
Commissioning (see "10Commissioning"[413])
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
CAUTION
Do NOT perform the test operation while working on
the indoor units.
When performing the test operation, NOT only the outdoor
unit, but the connected indoor unit will operate as well.
Working on an indoor unit while performing a test operation
is dangerous.
CAUTION
Do NOT insert fingers, rods or other objects into the air
inlet or outlet. Do NOT remove the fan guard. When the
fan is rotating at high speed, it will cause injury.
Maintenance and service (see "11Maintenance and
service"[413])
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
▪ Before carrying out any maintenance or repair activity,
ALWAYS switch off the circuit breaker on the supply
panel, remove the fuses or open the protection devices
of the unit.
▪ Do NOT touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.
▪ Please note that some sections of the electric
component box are hot.
▪ Make sure you do NOT touch a conductive section.
▪ Do NOT rinse the unit. This may cause electric shocks
or fire.
About the compressor
DANGER: RISK OF ELECTROCUTION
▪ Use this compressor on a grounded system only.
▪ Turn the power off before servicing the compressor.
▪ Reattach the switch box cover and service lid after
servicing.
CAUTION
Always wear safety goggles and protective gloves.
DANGER: RISK OF EXPLOSION
▪ Use a pipe cutter to remove the compressor.
▪ Do NOT use the brazing torch.
▪ Use approved refrigerants and lubricants only.
DANGER: RISK OF BURNING/SCALDING
Do NOT touch the compressor with bare hands.
Содержание
- Installation manual 1
- R32 split series 1
- 551 emc 2
- Daikin industries czech republic s r o 2
- Daikin tcf 32e12 06 2021 2
- Dekra nb0344 2
- Electromagnetic compatibility 2014 30 eu 2
- En60335 2 40 2
- Installation manual 2
- Low voltage 2014 35 eu 2
- Machinery 2006 42 ec 2
- P630134 7d 2
- Pressure equipment 2014 68 eu 2
- Rxta30b2v1b rxtm30r2v1b rxtm40r2v1b rxtp25r2v1b rxtp35r2v1b arxtp25r2v1b arxtp35r2v1b 2
- Tcf 0485a 01 2
- Vinçotte nv nb0026 2
- Jan olieslagerslaan 35 3
- Managing director 3
- P630134 7d 3
- Pilsen 1st of june 2021 3
- Vilvoorde belgium 3
- Vinçotte nv 3
- Yasuto hiraoka 3
- A subset of the latest technical data is available on the regional 4
- About the box 7 4
- About the documentation 4
- About the documentation 4 4
- About this document 4
- Always observe the following safety instructions and regulations 4
- And manuals product information 4
- Authorised installers 4
- Business portal authentication required 4
- Caution 4
- Charging refrigerant 10 4
- Commissioning 13 4
- Configuration 12 4
- Daikin website publicly accessible 4
- Disposal 14 4
- Documentation set 4
- Electrical installation 11 4
- Finishing the outdoor unit installation 12 4
- Format digital files on http www daikineurope com support 4
- Format paper in the box of the outdoor unit 4
- General safety precautions 4
- Information 4
- Installation instructions 4
- Installer reference guide 4
- Latest revisions of the supplied documentation may be available on the regional daikin website or via your dealer 4
- Maintenance and service 13 4
- Make sure installation servicing maintenance repair and applied materials follow the instructions from daikin and in addition comply with applicable legislation and are performed by qualified persons only in europe and areas where iec standards apply en iec 60335 2 40 is the applicable standard 4
- Make sure that the user has the printed documentation and ask him her to keep it for future reference 4
- Outdoor unit installation manual 4
- Piping installation 8 4
- Preparation of the installation reference data 4
- Safety instructions that you must read before installing 4
- Specific installer safety instructions 4
- Specific installer safety instructions 4 4
- Table of contents 4
- Target audience 4
- Technical data 14 4
- Technical engineering data 4
- The full set of latest technical data is available on the daikin 4
- The original documentation is written in english all other languages are translations 4
- This document is part of a documentation set the complete set consists of 4
- This document only describes installation instructions specific to the outdoor unit for installation of the indoor unit mounting the indoor unit connecting the refrigerant piping to the indoor unit connecting the electrical wiring to the indoor unit see the installation manual of the indoor unit 4
- To avoid injury do not touch the air inlet or aluminium fins of the unit 4
- To handle the outdoor unit see 3 to handle the outdoor unit 4 7 4
- Unit installation 7 4
- Warning 4
- Specific installer safety instructions 5
- Specific installer safety instructions 6
- About the box 7
- Installation site requirements of the outdoor unit 7
- Outdoor unit 7
- Preparing the installation site 7
- To handle the outdoor unit 7
- To remove the accessories from the outdoor unit 7
- Unit installation 7
- Additional installation site requirements of the outdoor unit in cold climates 8
- Mounting the outdoor unit 8
- Piping installation 8
- Preparing refrigerant piping 8
- Refrigerant piping requirements 8
- To install the outdoor unit 8
- To provide drainage 8
- To provide the installation structure 8
- Connecting the refrigerant piping 9
- Piping installation 9
- Refrigerant piping diameter 9
- Refrigerant piping insulation 9
- Refrigerant piping length and height difference 9
- Refrigerant piping material 9
- To connect the refrigerant piping to the outdoor unit 9
- About the refrigerant 10
- Charging refrigerant 10
- Checking the refrigerant piping 10
- To check for leaks 10
- To determine the additional refrigerant amount 10
- To perform vacuum drying 10
- Electrical installation 11
- To charge additional refrigerant 11
- To determine the complete recharge amount 11
- To fix the fluorinated greenhouse gases label 11
- Configuration 12
- Facility setting 12
- Finishing the outdoor unit installation 12
- Specifications of standard wiring components 12
- To connect the electrical wiring to the outdoor unit 12
- To finish the outdoor unit installation 12
- To set the facility mode 12
- Checklist before commissioning 13
- Checklist during commissioning 13
- Commissioning 13
- Maintenance and service 13
- To perform a test run 13
- Disposal 14
- Technical data 14
- Unified wiring diagram legend 14
- Winter season 14
- Wiring diagram 14
- Technical data 15
- Ped categories of equipment high pressure switch category iv compressor category ii other equipment art 4 3 16
- Piping diagram 16
- Piping diagram outdoor unit 16
- Technical data 16
Похожие устройства
- Daikin RXTP35R2V1B Инструкция по монтажу
- Daikin FTV25AV1 Инструкция по монтажу
- Daikin FTV35AV1 Инструкция по монтажу
- Daikin FTV50AV1 Инструкция по монтажу
- Daikin FTV60AV1 Инструкция по монтажу
- Daikin RV25AV1 Инструкция по монтажу
- Daikin RV35AV1 Инструкция по монтажу
- Daikin RV50AV1 Инструкция по монтажу
- Daikin RV60AV1 Инструкция по монтажу
- Gorenje B2470E Руководство по эксплуатации
- Prology CMX-230 Инструкция по эксплуатация
- Prology CMX-230 Краткое руководство пользователя
- Prology CMX-240 Инструкция по эксплуатация
- Prology iOne-3500 Инструкция по эксплуатация
- Prology iOne-3500 Краткое руководство пользователя
- Prology iOne-3000 Инструкция по эксплуатация
- Prology iOne-3000 Краткое руководство пользователя
- Prology iOne-2000 Инструкция по эксплуатация
- Prology iOne-2000 Краткое руководство пользователя
- Prology iOne-2500 Инструкция по эксплуатация