Daikin RHBX04CB [4/9] P383508 1b 2017 4

Daikin RHBX11CB [4/9] P383508 1b 2017 4
4/9
Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
A.3.1.2.2.1 [9-05] Temperature range Minimum temp (heating) R/W 15~37°C, step: 1°C
25°C
A.3.1.2.2.2 [9-06] Temperature range Maximum temp (heating) R/W 37~depending on outdoor unit, step: 1°C
55°C
A.3.1.2.2.3 [9-07] Temperature range Minimum temp (cooling) R/W 5~18°C, step: 1°C
5°C
A.3.1.2.2.4 [9-08] Temperature range Maximum temp (cooling) R/W 18~22°C, step: 1°C
22°C
└────────────────── Delta T source
A.3.1.3.1 [9-09] R/W 3~10°C, step: 1°C
5°C
A.3.1.3.2 [9-0A] R/W 3~10°C, step: 1°C
5°C
└─ Room thermostat
A.3.2.1.1 [3-07] Room temp. range Minimum temp (heating) R/W 12~18°C, step: A.3.2.4
12°C
A.3.2.1.2 [3-06] Room temp. range Maximum temp (heating) R/W 18~30°C, step: A.3.2.4
30°C
A.3.2.1.3 [3-09] Room temp. range Minimum temp (cooling) R/W 15~25°C, step: A.3.2.4
15°C
A.3.2.1.4 [3-08] Room temp. range Maximum temp (cooling) R/W 25~35°C, step: A.3.2.4
35°C
A.3.2.2 [2-0A] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.3 [2-09] R/W -5~5°C, step: 0,5°C
0°C
A.3.2.4 R/W 0: 0,5 °C
1: 1 °C
└─ Operation range
14~35°C, step: 1°C
25°C
(
*5
)
14~35°C, step: 1°C
35°C
(
*6
)
A.3.3.2 [F-01] R/W 10~35°C, step: 1°C
20°C
└─ Domestic hot water (DHW)
└─ Type
A.4.1 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
└─ Disinfection
A.4.4.1 [2-01] R/W 0: No
1: Yes
A.4.4.2 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunda
y
A.4.4.3 [2-02] R/W 0~23 hour, step: 1 hour
23
A.4.4.4 [2-03] R/W [E-07]
1 : 55~80°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
A.4.4.5 [2-04] R/W [E-07]1 : 5~60 min, step: 5 min
10 min
[E-07]=1 : 40~60 min, step: 5 min
40 min
└─ Maximum setpoint
A.4.5 [6-0E] R/W [E-07]1 : 40~80°C, step: 1°C
60°C
[E-07]=1 : 40~60°C, step: 1°C
60°C
└─ SP mode
A.4.6 R/W
0: Fixed
1: Weather de
p
.
└─ Weather dependent curve
A.4.7 [0-0B] Weather-dependent curve Leaving water value for high ambient temp. for
DHW WD curve.
R/W 35~[6-0E]°C, step: 1°C
55°C
A.4.7 [0-0C] Weather-dependent curve Leaving water value for low ambient temp. for
DHW WD curve.
R/W 45~[6-0E]°C, step: 1°C
60°C
A.4.7 [0-0D] Weather-dependent curve High ambient temp. for DHW WD curve. R/W 10~25°C, step: 1°C
15°C
A.4.7 [0-0E] Weather-dependent curve Low ambient temp. for DHW WD curve. R/W -40~5°C, step: 1°C
-10°C
└─ Heat sources
└─ Backup heater
A.5.1.1 [4-00] R/W 0~2
0: Disabled
1: Enabled
A.5.1.3 [4-07] R/W 0: No
1: Yes
A.5.1.4 [5-01] R/W -15~35°C, step: 1°C
0°C
└─ System operation
└─ Auto restart
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Preferential kWh rate
A.6.2.1 [D-00] R/W
0: None
1: BSH only
2: BUH only
3: All heaters
A.6.2.2 [D-05] R/W 0: Forced off
1: As normal
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
Allowed heaters
Forced pump OFF
Mode
Operation mode
Enable BUH step 2
Equilibrium temp.
Disinfection
Operation day
Start time
Temperature target
Duration
Room temp. step
A.3.3.1 [4-02] Space heating OFF temp R/W
Space cooling On temp
Heating
Cooling
Room temp. offset
Ext. room sensor offset
4P383508-1B - 2017.04
(*1) *HB*_(*2) *HV*_
(*3) *3V_(*4) *9W_
(*5) *04/08*_
(*6) *11/16*