Tecnoclima BESST/R 42 [22/40] Hydraulic connections

Tecnoclima BESST/R 21 [22/40] Hydraulic connections
22
HYDRAULIC CONNECTIONS
The choice and installation of the components is the installer’s
responsibility who must work according to the best practice rules and
the regulations in force. Before connecting the pipes, make sure they
do not contain stones, sand, rust, waste or anyway foreign bodies
which might damage the system.
A system “calibration” by-pass MUST be made for types 5-
6-7-8 and 13-14-15-16 (see drawing below). The by-pass
enables a better control of water flow-rate and lift, since the
provided pump is pre-equipped for a single speed.
System hydraulic connection diagram
1-2-9-10-type heat pump
F
F
3-4-5-6-7-8 type and 11-12-13-14-15-16 type heat pump
F
F
1 Pressure gauge
2 Antivibration coupling
3 Check valve
4 Mesh filter
5 Flow controller
6 Pump
7 Safety valve
8 Air vent
9 Expansion tank
10 Temperature probe
11 Fill/top up
12 Drain cock
13 Calibration by-pass (compulsory on 5-6-7-8 types and 13-14-
15-16 types)