Tecnoclima SUPERBESST 11 [21/40] Location

Tecnoclima BESST/R 21 [21/40] Location
21
LOCATION
The installation site must be determined by the system designer or a
competent person and must take into account technical requirements
and applicable laws and regulations which prescribe special
authorizations, (ex.: city planning, architectural, environmental
regulations, etc.).
It is therefore recommended to request and obtain the necessary
authorizations before installing the equipment.
The equipment must:
– be placed on an even surface which can support its weight.
– be placed on a sufficiently stiff floor slab which does not
transmit any vibration to the premises located under or adjacent
to it.
It is recommended to insert a rubber layer (hardness: 60 shores,
thickness: 10 mm) between floor slab and equipment, or use the anti-
vibration mounts available as an accessory.
The unit is destined for outdoor installation and must be located
within a buffer area in accordance with the figure below. The defined
clearances are required to enable a correct air flow and allow for
normal cleaning and maintenance operations.
It is advisable to avoid:
– the installation in skylight shafts and/or basement window wells
– obstacles or barriers causing the recycling of exhaust air
– the installation in sites with an aggressive atmosphere
– the installation in sites where the equipment noise may be
enhanced by reverberation or echoes
-
the installation in corners with settling of dust, leaves and whatever
may reduce the appliance efficiency, obstructing the air path
– the penetration of the equipment exhaust air into lived-in rooms
through doors or windows, causing trouble to people.
POSITION FOR ANTI-VIBRATION MOUNT FIXATION
B
A
A 1070 mm
TYPE 1-2-9-10
B 325 mm
A 1270 mm
TYPE 3-4-11-12
B 375 mm
A 1530 mm
TYPE 5-6-13-14
B 425 mm
A 1920 mm
TYPE 7-8-15-16
B 525 mm
Size 1-2-9-10 3-4-11-12 5-6-13-14 7-8-15-16
A 1000 1200 1500 1500 mm
B 500 600 700 700 mm
C 1000 1000 1000 1000 mm
D 600 800 800 800 mm
The area in front of the condensation fans must be totally
free from obstacles
If multiple appliances are installed side by side on the
external coil end, clearances must be summed up .
The two appliances should not be installed one with the fan
air supply facing the finned coil of the other