Daikin RZQ125B7W1B [8/48] Outdoor units r410a rzq b

Daikin RZQ100B8V3B [8/48] Outdoor units r410a rzq b
Outdoor Units • R410A • RZQ-B
Split Sky Air • Outdoor Units
6
2
2
Safety Devices High pressure switch High pressure switch
Fan motor thermal protector Fan motor driver overload protector
- Inverter overload protector
- Overcurrent relay
Fuse PC board fuse
Standard
Accessories
Item Tie-wraps Installation manual
Quantity 2211
Item Installation manual Additional refrigerant label
Quantity 1111
Item Installation manual Connection pipes
Quantity 1144
2-2 ELECTRICAL SPECIFICATIONS
RZQ71B8V3B RZQ100B8V3B RZQ100B7W1B RZQ125B8V3B
Power Supply Name V3 V3 W1B V3
Phase 1 1 3N 1
FrequencyHz50505050
Voltage V 230 230 400 230
Current Recomended fuses A 20 32 20 32
Voltage range Minimum V 207 207 360 207
Maximum V 253 253 440 253
Wiring
connections
For Power Supply Remark see installation manual 4PW21412-1
For connection
with indoor
Remark see installation manual 4PW21412-1
Power Supply Intake Outdoor unit only
2-2 ELECTRICAL SPECIFICATIONS
RZQ125B7W1B RZQ140B7W1B RZQ200B7W1B RZQ250B7W1B
Power Supply Name W1B W1B W1 W1
Phase 3N 3N 3N~ 3N~
FrequencyHz50505050
Voltage V 400 400 400 400
Current Nominal running
current
Cooling A - - refer to electrical data indoor outdoor combination
Heating A - - refer to electrical data indoor outdoor combination
Starting current (cooling/heating) - - refer to electrical data indoor outdoor combination
Maximum running current A - - refer to electrical data indoor outdoor combination
Recomended
fuses
A20203232
Voltage range Minimum V 360 360 360 360
Maximum V 440 440 440 440
Wiring
connections
For Power Supply Quantity - 5
Remark see installation manual 4PW21412-1 earth wire included
For connection
with indoor
Quantity - 4
Remark see installation manual 4PW21412-1 earth wire included
Power Supply Intake Outdoor unit only
Notes See seperate drawings for electrical data
Power supply to the FDQ indoor unit is separate
2-1 TECHNICAL SPECIFICATIONS
RZQ125B7W1B RZQ140B7W1B RZQ200B7W1B RZQ250B7W1B
NOTES
1 Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m,
level difference : 0m.
2 Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m,
level difference : 0m.