5.6.8 Vertical roof terminal and vertical flue system
Unit category: C33
CAUTION
If the vertical combi feedthrough cannot be applied, the air
supply and combustion gas outlet must be carried out
separately.
Vertical combi feedthrough.
Permitted pipe length
For parallel: Air supply and combustion gas outlet together, excluding the length of
the combi feedthrough.
For concentric: total pipe length, excluding the length of the combi feedthrough.
Parallel
Concentric
60/100
Concentric
80/125
EKOMB22AAV1
100 m
11 m
29 m
EKOMB28AAV1
85 m
10 m
29 m
EKOMB33AAV1
80 m
10 m
29 m
Combustion gas outlet and air supply pipe
For assembly, see par. 5.6.5 General assembly.
Assembly vertical roof terminal
1. Fit a vertical feed-through panel with scale at the location of the outlet on a
sloped roof.
A flat roof requires an adhesive panel for a Ø126 mm pipe.
2. Disassemble the manifold from the combi feedthrough.
3. Slide the combi feedthrough from outside to inside:
In case of a sloped roof, through the vertical feed-through panel with scale.
In case of a flat roof, through the adhesive panel.
4. In case of a parallel connection, fit the manifold of the combi feedthrough and
secure it with a sheet metal screw or pop rivet.