Daikin EKOMB33AAV1 [41/60] Parameter settings via the service code

Daikin EKOMB28AAV1 [41/60] Parameter settings via the service code
Daikin Europe NV
41
7.2 Parameter settings via the service code
The parameters of the boiler controller have been configured in the factory in accordance with
the following table.
These parameters can only be changed with the service code. Take the following actions to
activate the program memory:
1. Press the and the button simultaneously, until a
0
appears on the service display and a
0
on the temperature display.
2. Use the button to enter
15
(service code) on the temperature display.
3. Use the button to set the parameter you wish to configure, on the service display.
4. Use the and button to set the parameter to the required value (visible) on the temperature display.
5. After all the required changes have been entered, press the button until
P
appears on the service display.
The boiler controller has now been reprogrammed.
Note
Pressing the button will take you out of the menu without saving the parameter changes.
Example: Changing from ‘combi’ to ‘hot water only’
1. Press the and the button simultaneously.
2. Use the button to go to
15
.
3. Press the button 1 x. A 0 and a 1 will appear on the display.
4. Use the button to change the 0 to 2.
5. Press the button until
P
appears.
6. The change has now been implemented. The unit will only respond to a hot water request.
Para
-
EKOMB*AAV1
meter
Setting
22
28
33
0
Service code
[15]
-
-
-
Access to installers settings, the service code must be entered
(=15)
1
Installation type
0
0
0
0=
combi
1= space heating + hot water by means of storage tank
2 = hot water only
3 = space heating only
2
CH
pump continuous
0
0
0
0=
post
-
running
pump only
1= pump continuously active
2= pump continuously active with external MIT switch
3= pump continuously active with ext. power saving switch
3
Set maximum
CH
power
70
70
70
Setting reach set value parameter c
up to 85%
3.
80
80
80
Not applicable
4
Set maximum hot water power
99
99
99
Setting reach set value parameter d up to 100% (=99 + 1x
)
5
Min. leaving water temperature of the fuel
line
25
25
25
Setting reach 10°C to set value parameter 5
5.
Max
setting value leaving water
temperature via operating panel
90
90
90
Setting reach 30°C to 90°C
6
Min.
outdoor
temperature of the fuel line
-
7
-
7
-
7
Setting reach
-
9 to 10°C
7
Max.
outdoor
temperature of the fuel line
25
25
25
Setting reach 15°C to
30°C
8
CH
pump post
-
running time after
CH
operation
1
1
1
Setting reach 0 to 15 minutes
9
CH
pump post
-
running time after boiler
operation
1
1
1
Setting reach 0 to 15 minutes
(n/a for Combi unit)
A
Setting three
-
way valve or shut
-
off valve
MIT
0
0
0
0=
powered during CH operation
1= powered during hot water operation and rest
2= three-way valve in CH setting if device not in rest
3= zone regulation
4= External DHW tank pump
5= Powered during CH demand and rest
6= Powered during hot water operation
b
Booster
1
1
0
0= off
1= on
C
Step
-
by
-
step modulation
1
1
1
0= step
-
by
-
step modulation off during CH operation
1= step-by-step modulation on during CH operation
2= Power control by Open Therm room thermostat enabled
c
Minimum rpm CH
30
30
30
Settings
reach 20
50% (40%=propane)
c.
Activation external power saving switch
40
40
40
0= external
power saving switch input (connector X4, pos 4
-
5)