Daikin R2TND024A4AA [21/28] Installation

Daikin R2TND012A4AA [21/28] Installation
4 Installation
Installation manual
21
R2CND024A4AA + R2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-4E – 2017.07
g h
L
i j
a
b
c
b
d
e
f
a Flex kit PP Dn 60-80 or Dn 80
b Spacer
c Extension Flex PP 80mm
d Connector Flex-Flex PP 80mm
e Chimney connection 60/100 or 80/125
f 90° elbow 60/100
Optional:
g Tee 60/100 with measurement point
h 30° elbow 60/100
i 45° elbow 60/100
j Extension 80/125
L = 500-1000mm
Instead of 60/100, 80/125 flue ducts can be used at the outlet of the
boiler. In that case, the parts below are used:
a b c d e
a 60/100 to 80/125 adapter
b 90° elbow 80/125
c 45° elbow 80/125
d 30° elbow 80/125
e Extension 80/125
L = 500-1000mm
Allowable flue length for C93x (for R2CND* )
Shaft Chimney
cross-
section
Parameter
C3
“3” “5”
60-100
Concentric
circular and smooth 100 9.0 15.0
DN 60 Flex circular and rough 106 4.2 7.0
DN 60 Flex circular and rough 100 3.0 5.0
DN 60 Flex square and rough 95 4.2 7.1
DN 60 Flex square and rough 90 3.2 5.3
80-125
Concentric
circular and smooth 124 28.0 99.0
DN 80 Flex circular and rough 140 15.0 52.9
Allowable flue length for C93x (for R2CND* )
DN 80 Flex circular and rough 130 9.6 33.8
DN 80 Flex circular and rough 120 3.6 12.8
DN 80 Flex square and rough 140 19.6 69.2
DN 80 Flex square and rough 130 17.0 60.0
DN 80 Flex square and rough 120 12.2 43.0
DN 80 Star square and rough 140 47.5 167.8
DN 80 Star square and rough 120 33.3 117.9
Allowable flue length for C93x (for R2TND*)
Chimney cross-section PP 60mm rigid duct PP 60mm flexible
duct
Circular Ø100mm 7.2m 2.9m
Circular Ø120mm 9.3m 4.5m
Circular Ø140mm 9.9m 4.8m
Square 100×100mm 8.8m 5.1m
Square 120×120mm 9.7m 6.1m
Square 140×140mm 10.0m 6.2m
Chimney cross-section PP 80mm rigid duct PP 80mm flexible
duct
Circular Ø120mm 5.0m 5.0m
Circular Ø140mm 15.4m 15.4m
Circular Ø160mm 18.6m 18.6m
Square 120×120mm 5.0m 13.3m
Square 140×140mm 15.4m 18.3m
Square 160×160mm 18.6m 19.4m
Equivalent length of options
45° elbow 60/100mm 1.0m
90° elbow 60/100mm 1.5m
45° elbow 80/125mm 1.0m
90° elbow 80/125mm 1.5m
Maximum allowable length of the flue duct up to common
chimney is 2metres + 1 60/100 90° elbow.
Subtract equivalent length value of bends from the allowable flue
length value.
Type B53 (open flue system)
The boiler draws combustion air from the installation room and
expels flue gas through the flue to above the roof (1).
The boiler draws combustion air from the installation room and
routes flue gas through the moisture-resistant chimney to above the
roof (2).
Allowable flue length for B53
R2TND* R2CND*
Flue duct 60mm 24.0m 20.0m
Flue duct 80mm 130.0m 112.0m