4 Installation
Installation manual
9
R2CND024A4AA + R2TND012~024A4AA
Wall-mounted condensing boiler
3P469346-4E – 2017.07
a
a Vertical, flat wall
▪ The boiler can be installed outdoors in a partially protected
location. A partially protected location is a place where the boiler
is not exposed to the direct action and to the penetration of
atmospheric precipitation (rain, snow, hail,...).
The boiler can also be installed inside of an outside wall using the
appropriate in‑wall kit.
In case of outdoor installation, use the antifreeze kit
(DRANTIFREEZAA) to prevent the piping and condensate trap
from freezing.
▪ Flammable fluids and materials must be stored at least 1 metre
away from the boiler.
▪ The wall on which the unit is mounted should be strong enough to
carry the unit's weight. Build a reinforcement if necessary.
▪ The following minimum clearances are required for servicing:
180mm above the casing*, 200mm below, and 10 mm at each
side. 500mm at the front clearance may be realised by opening a
cupboard door. See "Minimum installation clearances" on
page9.
▪ For easier use of control panel, it is recommended that boiler
bottom is 1500mm from the floor, for easier part replacement side
clearances should be 50 mm where applicable. See "Minimum
installation clearances"on page9.
▪ If the boiler is installed in a room or compartment, it does not
require a dedicated ventilation for combustion air. If however
installed in a room containing a bath or a shower, then particular
reference is drawn to the current I.E.E. Wiring Regulations, local
Building Regulations or any other local regulations currently in
service.
▪ The intake air must not include chemicals that may cause
corrosion, toxic gas formation and even risk of explosion.
▪ If the wall on which the unit is mounted, is flammable, a non-
flammable material must be placed between the wall and the unit
and also at all locations through where the flue piping passes.
Minimum installation clearances
a a
d
f
c
e
d
b
Minimum allowable clearances
a, sides 10mm
b, Above the casing* 180mm
c, below 200mm
f, in front 500mm
Recommended clearances for easy servicing
d, sides 50mm
e, below (from the floor) 1500mm
* 180mm is for the case that 60/100 90° elbow is connected
to the flue outlet of the boiler.
b = 270mm in case that 60/100 to 80/80 adapter + 90°
elbow 80 are connected to the flue outlet of the boiler.
b = 280mm in case that 60/100 to 80/125 adapter + 90°
elbow 80/125 are connected to the flue outlet of the boiler.
4.3 To unpack the unit
1 Unpack the unit as shown on top of the packing case. The
following items must be included in the package:
a b c d e f g h i j
a Combi boiler
b Operation manual
c Installation manual
d Wall-mounting bracket
e Installation template
f Dowels and screws
g Condensate hose
h Cable glands 2×PG7, 1×PG9
i Energy label
j Storage tank temperature sensor (only for models
R2TND012A4AA, R2TND018A4AA and R2TND024A4AA)
2 Check the contents of the package. If any of them is damaged
or missing, contact your dealer.
CAUTION
Store the remaining parts of the package (cardboard,
plastic, etc.) in a place children cannot reach. The
manufacturer is not responsible for any accidents and/or
damage that may occur this way.
Содержание
- Installation manual 1
- Wall mounted condensing boiler 1
- 02 94005 02 2
- Boiler efficiency 92 42 eec 2
- Electromagnetic compatibility 2014 30 eu 2
- En15502 1 en60335 2 102 2
- Gas appliances 2009 142 ec 2
- Georg blümel 2
- Installation manual 2
- Kiwa nb0063 2
- Low voltage 2014 35 eu 2
- Managing director 2
- P475131 2b 2
- R2cnd028 r2tnd028 r2cnd035 r2tnd035 2
- R2tnd012 r2tnd018 r2cnd024 r2tnd024 2
- Rd of july 2017 2
- Tcf 01 6 2
- About the documentation 3
- About the unit 4 3
- Caution 3
- Commissioning 24 3
- Danger 3
- Disposal 3
- Hand over to the user 25 3
- Identification label 3
- Indicates a situation that could result in death or serious injury 3
- Indicates a situation that could result in equipment or property damage 3
- Indicates a situation that could result in minor or moderate injury 3
- Indicates a situation that results in death or serious injury 3
- Indicates useful tips or additional information 3
- Information 3
- Installation 8 3
- Installers and they cover very important topics follow them carefully 3
- Introduction 3
- Introduction 3 3
- Languages are translations 3
- Meaning of warnings and symbols 3
- Notice 3
- Old units must be appropriately disposed of in accordance with local and national regulations the components are easy to separate and the plastics are marked this allows the various components to be sorted for appropriate recycling or disposal 3
- Please read the operation manual and installation manual prior to 3
- Safety instructions 4 3
- Table of contents 3
- The instructions contained in this document are intended to guide you through the installation of the unit damage caused by non observance of these instructions are not under the responsibility of rotex 3
- The original documentation is written in english all other 3
- The precautions described in this document are written for 3
- This means that electrical and electronic products may not be mixed with unsorted household waste do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation units must be treated at a specialized treatment facility for reuse recycling and recovery by ensuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health for more information contact your installer or local authority 3
- Units are marked with the following symbol 3
- Use and keep them for future reference 3
- Warning 3
- You can find data about the unit on its identification label which is located at the bottom of the right cover of the unit 3
- About the unit 4
- Safety instructions 4
- Safety systems 4
- Symbols on the package 4
- About the unit 5
- Dimensions 5
- About the unit 6
- Components 6
- Components of model r2cnd024a4aa 6
- Components of models r2tnd012a4aa r2tnd018a4aa and r2tnd024a4aa 6
- A 20 30 for hungary 7
- About the unit 7
- Installation manual 7
- R2cnd024a4aa r2tnd012 024a4aa wall mounted condensing boiler 3p469346 4e 2017 7 7
- Technical specifications 7
- A control panel 8
- A front cover 8
- A high temperature regime means 60 c return temperature at heater inlet and 80 c feed temperature at heater outlet 8
- B low temperature means for condensing boilers 30 c for low temperature boilers 37 c and for other heaters 50 c return temperature at heater inlet 8
- Certain actions explained in this document such as gas conversion optional equipment connection require that the front cover is opened 8
- Dismantle the two mounting clips that hold the front cover 2 8
- Installation 8
- Installation manual 8
- Installation site requirements 8
- Loosen the screw that holds the right mounting clips 1 8
- Loosen the two screws of the control panel 4 8
- Mount this unit on vertical flat walls only 8
- Only qualified competent persons are allowed to open the unit 8
- P469346 4e 2017 7 8
- R2cnd024a4aa r2tnd012 024a4aa 8
- Remove the front cover forwards 3 8
- Shift the control panel downwards 5 and then pull it forwards 6 8
- The boiler must be installed by a qualified installer in accordance with local and national regulations 8
- The following instructions shall be observed when determining the installation site 8
- To open the unit 8
- Wall mounted condensing boiler 8
- Warning 8
- Installation 9
- Minimum installation clearances 9
- To unpack the unit 9
- Central heating system requirements 10
- Installation 10
- To mount the unit 10
- Connections 11
- Installation 11
- Piping connections 11
- Residual pump lift graph 11
- Underfloor heating requirements 11
- B f d e 12
- Guidelines when connecting the gas piping 12
- Guidelines when connecting the water piping 12
- Installation 12
- Guidelines when connecting options to the boiler 13
- Guidelines when connecting the electrical wiring 13
- Installation 13
- Installation 14
- Installation 15
- Wiring diagram 15
- Guidelines for condensate piping termination 16
- Guidelines when connecting the condensate piping 16
- Installation 16
- Applicable flue systems 17
- Guidelines when connecting the boiler to the flue gas system 17
- Installation 17
- Type c13x concentric flue system 17
- 125 mm flue system 18
- Installation 18
- Type c33x concentric flue system 18
- Installation 19
- Type c43x concentric flue system 19
- Type c53x twin pipes flue system 19
- Type c63x concentric flue system 19
- Installation 20
- Type c83x twin pipes flue system 20
- Type c93x 20
- Installation 21
- Type b53 open flue system 21
- Flue parts order codes 22
- Installation 22
- Type b33 open flue system 22
- Converting for use with a different type of gas 23
- Installation 23
- To fill the system with water 23
- Commissioning 24
- Gas air ratio no need to adjust 24
- To check for gas leakage 24
- To commission the unit 24
- To convert the system for use with a different type of gas 24
- To fill the condensate trap 24
- To modify settings for gas conversion 24
- Hand over to the user 25
- To commission the central heating 25
- To commission the central heating capacity setting 25
- To commission the domestic hot water 25
- P469346 4e 28
- Subject to change and correction 28
Похожие устройства
- Samsung Galaxy Z Fold3 256GB Black (SM-F926B) Руководство пользователя
- Samsung Galaxy Z Flip3 128GB Beige (SM-F711B) Руководство пользователя
- Wolta STD ДПО13-36-101-4К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-36-101-4К Презентация
- Wolta STD ДПО13-36-101-5К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-36-101-5К Презентация
- Wolta STD ДПО13-36-101-6К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-36-101-6К Презентация
- Wolta STD ДПО13-36-102-4К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-36-102-4К Презентация
- Wolta STD ДПО13-36-102-5К Презентация
- Wolta STD ДПО13-36-102-5К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-36-102-6К Презентация
- Wolta STD ДПО13-36-102-6К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-54-101-4К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-54-101-4К Презентация
- Wolta STD ДПО13-54-101-5К Презентация
- Wolta STD ДПО13-54-101-5К Руководство по монтажу и эксплуатации
- Wolta STD ДПО13-54-101-6К Презентация
- Wolta STD ДПО13-54-101-6К Руководство по монтажу и эксплуатации