Addendum to installation manual
3
EKHBRD011~016ADV1+Y1
4P402187-1B – 2015.09
9 Automatic temperature compensation
00 Leaving water temperature compensation value
(heating)
0 –2~2 0.2 °C
01 Domestic hot water tank compensation value 0 –5~5 0.5 °C
02 Thermo ON/OFF admission 0 –5~5 0.5 °C
03 Not applicable. Do not change the default value. 0
04 Not applicable. Do not change the default value. 0
A Option setup
00 Current limitation. 0 0~2 1
01 Not applicable. Do not change the default value. 0
02 Set point: heating required temperature difference
for leaving and returning water
10 3~15 1 °C
03 Set point: multiple set point 1 required temperature
value
35 25~80 1 °C
04 Set point: multiple set point 2 required temperature
value
65 25~80 1 °C
b Domestic hot water set points
00 Set point: reheat minimum temperature 35 35~65 1 °C
01 Set point: reheat maximum temperature 45 35~75 1 °C
02 Status: weather dependent domestic water
heating
1 (ON) 0/1
03 Set point: storage temperature 70 45~75 1 °C
04 Automatic maximum domestic hot water storage
temperature
70 55~75 1 °C
C Leaving water temperature limits
00 Set point: heating leaving water maximum
temperature
80 37~80 1 °C
01 Set point: heating leaving water minimum
temperature
25 25~37 1 °C
02 Not applicable. Do not change the default value. 20
03 Not applicable. Do not change the default value. 5
04 Not applicable. Do not change the default value. 0
d Domestic water heating retention times
00 Set point: minimum time for domestic water
heating
10 5~20 1
01 Set point: maximum time for domestic water
heating
30 10~60 5
02 Set point: interval minimum stop time of domestic
water heating
15 5~30 5
03 Not applicable. Do not change the default value. 15
04 Not applicable. Do not change the default value. 40
E Service mode
00 Vacuum mode R134a 0 0/1
01 Not applicable. Do not change the default value. 0
02 Not applicable. Do not change the default value. 0
03 Not applicable. Do not change the default value. 1
04 Pump only operation 0 0~25 1
F Option setup continued
00 Not applicable. Do not change the default value. 5
01 Not applicable. Do not change the default value. 0
02 Not applicable. Do not change the default value. 1
03 Not applicable. Do not change the default value. 10
04 Not applicable. Do not change the default value. 50
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value