2.4.5 Heating and sanitary side connection
● Create a heating system according to the
safety requirements of EN 12828.
● With a sanitary connection you must comply
with
–EN 1717 – Protection against pollution of
potable water installations and general
requirements of devices to prevent pollu-
tion by backflow
–EN 806 – Specifications for installations
inside buildings conveying water for human
consumption
– and, in addition, the country-specific legal
stipulations.
The connection of a solar installation, an electric
heating rod or an alternative heat generator may
cause the storage temperature to exceed 60 °C.
● For this reason you should fit scalding
protection (e.g. VTA32 + Screw connection
set 1") during installation.
● Use a pressure reducer if the cold water
connection
pressure >6 bar.
If the Daikin EKHWP / EKHWC / EKHWD is
connected to a heating system with steel pipes,
radiators or non-diffusion-proof floor heating
pipes, slurry and swarf could enter the hot water
storage tank and cause blockages, local
overheating or corrosion.
● To prevent possible damage, fit a dirt filter or
sludge separator into the heating return flow
of the system.
–SAS 1
2.4.6 Operation
● Only operate the Daikin EKHWP / EKHWC /
EKHWD:
– After all installation and connection work
has been completed.
– With fully installed equipment covers and
service accesses.
– With sanitary side pressure reducers
installed (max. 6 bar).
– With heating side pressure reducers
installed (max. 3 bar).
– With completely filled storage containers
(fill level display).
The prescribed maintenance intervals must be
maintained and the inspection work must be
carried out.
2.4.7 Instruct the owner
● Before you hand over the heating system and
the hot water storage tank, explain to the
owner how he/she can operate and check the
heating system.
● Provide the operator with the technical
documentation (this documentation and all its
references) and indicate that these
documents must be available in the
immediate vicinity of the unit at all times.
● Document the hand-over by filling in and
signing the checklist in chapter 5 "Start-up",
together with the operator.
2.4.8 Documentation
The technical documentation contained in the
scope of supply is part of the device. It must be
stored in such a way that it can be consulted at
any time by the operator or the technicians.
The domestic water quality must comply
with the EU Guideline 98/83 EC and the
regional applicable regulations.
Содержание
- High efficiency hot water storage tank 1
- Installation and operating instructions 1
- Annual inspection 25 3
- Avoiding danger 3
- Basic data 26 3
- Brief description 3 3
- Connection diagrams 23 3
- Design and components 3
- Draining the storage tank 1 3
- Filling topping up 8 3
- Final shutdown 2 3
- General information 3
- Hydraulic connection 3 3
- Installation 5 3
- Installation 6 3
- Instructions for operating safety 3
- List of contents 3
- List of keywords 5 3
- Notes 3 3
- Optional accessories 4 3
- Performance diagrams 31 3
- Periodic checks 25 3
- Product description 3
- Refer to the manual 3
- Safety 3
- Scope of delivery 3 3
- Service and maintenance 5 3
- Set up and installation 5 3
- Start up 0 3
- Taking out of operation 1 3
- Technical data 6 3
- Temporary shutdown 1 3
- Tightening torque 32 3
- Use as intended 3
- Warning signs and explanation of symbols 3
- General information 4
- Refer to the manual 4
- Relevant documents 4
- X general information 4
- Avoiding danger 5
- Handling instructions 5
- Meaning of the warnings 5
- Safety 5
- Validity 5
- Warning signs and explanation of symbols 5
- X safety 5
- Before working on the hot water storage tank and the heating system 6
- Electrical installation of optional accessories 6
- Housing installation room 6
- Instructions for operating safety 6
- Requirements of the heating and filling water 6
- Use as intended 6
- X safety 6
- Documentation 7
- Heating and sanitary side connection 7
- Instruct the owner 7
- Operation 7
- X safety 7
- Design and components 8
- Product description 8
- X product description 8
- High performance hot water storage tank for heat pump systems 9
- Non pressurised system drainback 9
- X product description 9
- Fig 3 2 connections and dimensions high performance hot water storage tank with solar support type ekhwp 300 500bp 10
- Pressurised system 10
- X product description 10
- High performance hot water storage tank for all heat sources excluding low temperature heat pumps 11
- Non pressurised system drainback 11
- X product description 11
- Pressurised system 12
- X product description 12
- Brief description 13
- Economical operation 13
- Electronic control 13
- Low maintenance and corrosion 13
- Low scaling 13
- Modular extension facility 13
- Optimum water hygiene 13
- Scope of delivery 13
- X product description 13
- Dirt filters 14
- Electric immersion heaters 14
- Flowguard flg 14
- For convenient filling and draining of the daikin hot water storage tank you can connect the kfe filling connection kfe ba 14
- For ekhwc ekhwd 14
- For ekhwp booster heater 14
- If the daikin high performance hot water storage tank is con nected to a heating system with steel pipes radiators or non dif fusion proof floor heating pipes slurry and swarf could enter the hot water storage tank and cause blockages local overheating or corrosion this can be prevented by fitting a dirt filter or sludge trap see daikin price list 14
- If the heat output of a single daikin hot water storage tank is not adequate you can interconnect several ekhwp ekhwc ekhwd modules 14
- In addition to the heating capability via the corrugated stainless steel pipe heat exchanger and various different heat sources and energy carriers the daikin high performance hot water storage tank can also be charged using an electric immersion heater 14
- Kfe filling connection 14
- Non return valves 14
- Optional accessories 14
- Scalding protection 14
- Scalding protection vta32 14
- Screw connection set 1 14
- Solar storage tank extension kit 14
- Solar storage tank extension kit 2 con sxe 14
- Solar storage tank extension kit con sx 14
- The following components are offered 14
- The installation and operation of this accessory component is de scribed in detail in the individual operating and installation in structions provided 14
- There is a danger of scalding at hot water temperatures over 60 c fitting scalding protection enables the hot water temper ature to be varied continuously and limited from 35 60 c 14
- This means that both the stainless steel heat exchangers for post heating and the hot water heat exchangers are intercon nected in accordance with the tichelmann principle chapter 7 hydraulic connection 14
- To prevent heat loss from the connection pipes when the circu lation pump is switched off and during periods when no domestic water is drawn off gravity circulation you should fit circulation brakes in the connections for the daikin high performance hot water storage tank see tab 3 1 14
- With seasonal variations in demand these individual units can be added or taken out of service accordingly in this way the total hot water output can be manually matched to the actual demand 14
- X product description 14
- Important information 15
- Installation 15
- Installing the hot water storage tank 15
- Set up and installation 15
- X set up and installation 15
- Important information 16
- Installation 16
- X set up and installation 16
- Hydraulic system connection 17
- X set up and installation 17
- All ekhwd hot water storage tanks 18
- Buffer tank 18
- Caution 18
- Ekhwp ekhwc hot water storage tank without 18
- Filling topping up 18
- Hot water heat exchanger 18
- If filling or topping up the storage tank is done by means of the boiler filling and drain valve a temporary filling loop must be used with the appropriate backflow prevention device in accordance with clause g24 guidance to the water supply water fittings regulations 1999 18
- If there is an electric immersion heater booster heater or regulation and pump station installed in the hot water storage tank then these components must be isolated from the power supply before starting the work e g fuse main switch switched off and secured against inadvertent switching on again 18
- Live parts can cause an electric shock on contact and cause fatal burns or injuries 18
- Solar system and without kfe filling connection kfe ba 18
- Warning 18
- X set up and installation 18
- Ekhwp ekhwc hot water storage tank with solar system 19
- X set up and installation 19
- A hot water storage tank commissioned im properly can lead to property damage 20
- Caution 20
- For filling and top up water with high water hardness take measures for softening the water or stabilising hardness 20
- If the booster heater is started with the storage tank empty or not completely full it can lead to a reduction in performance of the electric heating tripping of the safety temperature limiter 20
- Installation commissioning may only be carried out by authorized and trained heating technicians following the installation and maintenance manual included 20
- Observe the regulations in vdi 2035 in order to avoid corrosion and deposits 20
- Only original daikin replacement parts may be used 20
- Operate the electric immersion heater booster heater only with the storage tank completely full 20
- Set the pressure reducer on the cold water connection to a maximum of 6 bar 20
- Start up 20
- Units which have been set up and installed incorrectly may not operate properly and can be a health and safety risk endangering human life 20
- Warning 20
- X start up 20
- A heating system which is shut down can freeze in the event of frost and may suffer damage 21
- Allow the hot water storage tank to cool down adequately before any installation work 21
- Caution 21
- Danger of scalding caused by emerging hot water from the storage tank 21
- Draining the storage tank 21
- In the event of a danger of frost start the entire daikin heating system up again and activate the frost protection function or take the appropriate frost protection measures for the hot water storage tank e g by draining 21
- Taking out of operation 21
- Temporary shutdown 21
- Warning 21
- Wear protective gloves 21
- With pre mounted kfe filling connection 21
- With solar system 21
- With subsequently fitted kfe filling connection 21
- Without kfe filling connection 21
- Without solar system 21
- X taking out of operation 21
- Caution 22
- Drain the solar panel circuit only pressurised system 22
- Draining the heating circuit and hot water circuit 22
- Final shutdown 22
- If heat transfer media containing glycol are ex posed to temperatures above 170 c over an extended period they will decompose or form silt this may reduce the frost protection affect the output of the solar system and damage com ponents of the system 22
- In the event of extended standstill of the solar panel circuit drain in accordance with the installation instructions of the regulating and pump unit 22
- Recommendations for disposal 22
- Storage water will gush out as soon as the seal ing plug is removed 22
- There is no valve and no non return flap on the filling and draining connection 22
- X taking out of operation 22
- Connection diagrams 23
- Hydraulic connection 23
- Solution for low temperature heat pumps 23
- X hydraulic connection 23
- X hydraulic connection 24
- All work performed on live components must be carried out in accordance with the proper proce dures otherwise there may be a danger to the life and health of individuals and the function may be impaired 25
- Annual inspection 25
- If there is an electric immersion heater booster heater or regulation and pump station installed in the hot water storage tank then these components must be isolated from the power supply before starting the inspection and maintenance work e g fuse main switch switched off and secured against inadvertent switching on again 25
- Live parts can cause an electric shock on contact and cause fatal burns or injuries 25
- Periodic checks 25
- Rectification of damage to live components may only be carried out by heating engineers authorised and recognised by the energy supply company 25
- Service and maintenance 25
- Warning 25
- X service and maintenance 25
- Basic data 26
- Technical data 26
- X technical data 26
- Non pressurised drainback db 27
- X technical data 27
- Pressurised system p 28
- X technical data 28
- Non pressurised drainback db 29
- X technical data 29
- Pressurised system p 30
- X technical data 30
- Ekhwd ekhwc 31
- Ekhwd ekhwc 9 ekhwp 31
- L min can in certain rare circum stances lead to noises in the domestic water heat exchanger of the hot water storage tank 31
- Performance diagrams 31
- X technical data 31
- Tightening torque 32
- X technical data 32
- X notes 33
- X notes 34
- List of keywords 35
- Numerics 35
- X list of keywords 35
Похожие устройства
- Rekam ILOOK 500 Руководство пользователя
- Rekam ILOOK 555 Руководство пользователя
- Rekam ILOOK 735 Руководство пользователя
- Rekam PRESTO ML60 Руководство пользователя
- Rekam PRESTO ML65 Руководство пользователя
- Rekam PRESTO ML100 Руководство пользователя
- Rekam PRESTO SL6 Руководство пользователя
- Rekam PRESTO SL65 Руководство пользователя
- Rekam PRESTO SL70 Руководство пользователя
- Rekam PRESTO SL80 Руководство пользователя
- Rekam PRESTO SL120 Руководство пользователя
- Rekam PRESTO SLX5 Руководство пользователя
- Onkyo TX-8030 Руководство пользователя
- Onkyo TX-NR414 Руководство пользователя
- Onkyo TX-NR515 Руководство пользователя
- Onkyo TX-NR 818 Руководство пользователя
- Rolsen RСA-510 Руководство пользователя
- Rolsen RDV-790K Руководство пользователя
- Rolsen RDR-430 Руководство пользователя
- Rolsen RDR-410 Руководство пользователя