Packaged Rooftop
22
We reserve the right to make changes without any prior notice.
UATYA
4P645203-1
“cascade”temperaturecontrol.
If parameter “ST11” is set to “1”, “Cascade” control is enabled.
This function fulls the system demand and keeps the air temperature in the delivery line within comfort values.
For this purpose, a virtual setpoint is calculated from the stored setpoint, as corrected with the air temperature in the
return line.
The setpoint is corrected dynamically as the air temperature changes in the delivery line.
The parameters involved in cascade temperature control are shown in the table.
The values of the parameters are representative. In specic cases, di󰀨erent values can be set.
Parameter Value UM Description
ST42 24.0 °C Cascade control - Unit setpoint
ST43 0.5 °C Mechanical cooling - Cascade control - Mode switching o󰀨set
ST44 4.0 °C Mechanical cooling - Cascade control - Operating di󰀨erential
ST45 15.0 °C Mechanical cooling - Cascade control - Min. delivery setpoint
The graph below illustrates cascade control.
Spd °C
ST45
ST43
Tra °C
ST44
ST42
ST42
AOC
Fig. 5 Change of air delivery setpoint with “cascade” control in cooling mode
In addition to the parameters listed in the table, the abbreviations in the graph are:
- Spd = air setpoint in delivery line;
- Tra = air temperature in return line;
- AOC = automatic mode switching.