CODE DESCRIPTION MAIN CAUSES CHECKS AND TROUBLESHOOTING RESET
UNIT
OFF
ITEMS OFF
AL24
B7 probe broken or
disconnected
The reading of the probe B7
(indoor air humidity) exceeds
the range
Check working conditions.
M No
All components and
fuctions directly
related to the probe
Check in the controller for the correct
probe reading range .
Check the correct reading of the probe
and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic
input of the main board.
AL25
B4 probe broken or
disconnected
The reading of the probe
B4 (supply air temperature)
exceeds the range
Check working conditions.
M No
All components and
fuctions directly
related to the probe
Check in the controller for the correct
probe reading range .
Check the correct reading of the probe
and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic
input of the main board.
AL26
B3 probe broken or
disconnected
The reading of the probe B3
(condensing pressure circuit
1) exceeds the range
Check working conditions.
M No
All components and
fuctions directly
related to the probe
Check in the controller for the correct
probe reading range .
Check the correct reading of the probe
and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic
input of the main board.
AL27
B8 probe broken or
disconnected
The reading of the probe B8
(Outdoor air temperature)
exceeds the range
Check working conditions.
M No
All components and
fuctions directly
related to the probe
Check in the controller for the correct
probe reading range .
Check the correct reading of the probe
and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic
input of the main board.
AL28
B5 probe broken or
disconnected
The reading of the probe
B5 (return air temperature)
exceeds the range
Check working conditions.
M No
All components and
fuctions directly
related to the probe
Check in the controller for the correct
probe reading range .
Check the correct reading of the probe
and eventually replace it.
Check probe wiring and terminals.
Check correct functioning of the analogic
input of the main board.
AL29 Heater 1 overload
The circuti breaker of the
heater group 1 trips
Checkworkingconditions(airowand
temperature).
M No Heater group 1Check cabling and terminals of the
heaters and adsorbed current.
Check thermal switch.
AL30 Heater 2 overload
The circuit breaker of the
heater group 2 trips
Checkworkingconditions(airowand
temperature).
M No Heater group 2Check cabling and terminals of the
heaters and adsorbed current.
Check thermal switch.
AL31
Generic serious
alarm by DIN .
Systemo󰀨
The serious alarm digital input
(DIN) is open
Check external control. M Yes All
AL32
Generic alarm by
dig. input System
still on
The generic alarm digital input
is open
Check extarnal control. M No None