enable the weekly programming, if required.
set week days when the unit has to be in ON status (Y) or in OFF status (N).
2.5.1 Time slots programming examples
To better explain the time slots programming, two examples are reported in the following.
Example n. 1
Theunithastooperateeveryday:
from07:00to20:00withsummersetpoint26.0°Candwintersetpoint21.0°C;
from20:00to07:00withsummersetpoint30.0°Candwintersetpoint15.0°C.
Moreover, unit main fans must be always active.
MasksK2toK6havetobesetasfollows:
It is not required to set working days on mask K7, because weekly programming is disabled from mask K6.