Daikin SB.LBWWHD030AV3096 [10/56] F gas regulation

Daikin SB.LBWWHD050AV3096 [10/56] F gas regulation
10
F-gas
regulation
What does the F-Gas regulation mean?
Stationary
refrigeration equipment
GWP < 2500
Common commercial HFC refrigerants:
R-134a, R-407A, R-407C, R-407F, R-410A
GWP > 2500
Common commercial HFC refrigerants:
R-404A, R-507
GWP
2500
Stationary
refrigeration equipment
(= systems which are not
in transit during operation)
From 2020:
use refrigerants with
GWP <2500
Is it a domestic
refrigerator?
From 2015:
use refrigerants
with GWP < 150
Is it a multi-pack
centralised refrigeration
system*?
Use regerants with
GWP < 2500
Is it an
integral / plug-in?
From 2020:
use refrigerants with GWP < 2500
From 2022:
use refrigerants with GWP < 150
YES
YES YESNO
NO
NO
Ban from the year 2020 onwards
in new stationary refrigeration equipment
Ban from the year 2030 onwards
in servicing existing stationary refrigeration equipment
FOLLOW THE DECISION TREEE
* “Multipack centralised refrigeration systems” = Systems with two or more compressors operated in parallel,
which are connected to one or more common condensers and to a number of cooling devices such as display cases, cabinets, freezers or to chilled store rooms.