Mask Index Description Value UOM Type Channel Min Max Offset
Cab01 L1 Compressors regulation type PROPORTIONAL BAND
Cab01 L1 Compressors control mode --
Cab02 L1 Minimum suction setpoint
Cab02 L1 Maximum suction setpoint
Cab03 L1 Setpoint chiller running 0
Cba05 L1 Suction differential 0
Cab08 L1 Increasing zone differential for compressors regulation (neutral zone) 0
Cab08 L1 Decreasing zone differential for compressors regulation (neutral zone) 0
Cab12 L1 Compressors neutral zone minimum complete activation time (neutral zone) 0 s
Cab12 L1 Compressors neutral zone maximum complete activation time (neutral zone) 256 s
Cab13 L1 Compressors neutral zone minimum complete deactivation time (neutral zone) 0 s
Cab13 L1 Compressors neutral zone maximum complete deactivation time (neutral zone) 0 s
Cad08 L1 Enable floating suction setpoint compensation 0 NO
Cad09 L1 Floating suction maximum setpoint 0
Cad09 L1 Floating suction minimum setpoint 0
Cad10 L1 Floating suction maximum delta admitted 0
Caf02 L1 Compressors type 0 RECIPROCATING
Caf02 L1 Number of compressors 1 -
Caf04 L1 Suction refrigerant type 0 R22
Caf10 L1 Compressors rotation type 0 -
Caf15 L1 Compressors modulating device type 0 NONE
Caf91 L1 Compressors size 1 0
Caf91 L1 Compressors size 2 0
Caf91 L1 Compressors size 3 0
Caf91 L1 Compressors size 4 0
Caf16 L1 Compressors inverter minimum frequency 10 Hz
Caf16 L1 Compressors inverter maximum frequency 850 Hz
Cag01 L1 Compressors inverter minimum voltage 0
Cag01 L1 Compressors inverter maximum voltage 0
Cag01 L1 Compressors inverter nominal frequency 0 Hz
Cag01 L1 Compressors inverter nominal power 0
Cag02 L1 Compressors inverter rising time 0 s
Cag02 L1 Compressors inverter falling time 0 s
************ -- --
L2 - COMPRESSORS -- --
************ -- --
Cbb01 L2 Compressors regulation type 0 PROPORTIONAL BAND
Cbb01 L2 Compressors control mode 0 PRESSURE
Cbb02 L2 Minimum suction setpoint 18
Cbb02 L2 Maximum suction setpoint 0
Cbb03 L2 Suction setpoint 0
Cbb05 L2 Suction differential 100
Cbb08 L2 Increasing zone differential for compressors regulation (neutral zone) 0
Cbb08 L2 Decreasing zone differential for compressors regulation (neutral zone) 0
Cbb12 L2 Compressors neutral zone minimum complete activation time (neutral zone) 150 s
Cbb12 L2 Compressors neutral zone maximum complete activation time (neutral zone) 65531 s
Cbb13 L2 Compressors neutral zone minimum complete deactivation time (neutral zone) 0 s
Cbb13 L2 Compressors neutral zone maximum complete deactivation time (neutral zone) 0 s
Cbd08 L2 Enable floating suction setpoint compensation 1 YES
Cbd09 L2 Floating suction maximum setpoint 5
Cbd09 L2 Floating suction minimum setpoint 0
Cbd10 L2 Floating suction maximum delta admitted 2
Cbf02 L2 Compressors type 0 RECIPROCATING
Cbf02 L2 Number of compressors 3 -
Cbf04 L2 Suction refrigerant type 2
Cbf10 L2 Compressors rotation type 0 -
Cbf15 L2 Compressors modulating device type 0 NONE
Cbf41 L2 Compressors size 1 0
Cbf41 L2 Compressors size 2 0
Cbf41 L2 Compressors size 3 0
Cbf41 L2 Compressors size 4 0
Cbf16 L2 Compressors inverter minimum frequency 1 Hz
Cbf16 L2 Compressors inverter maximum frequency 256 Hz
Cbg01 L2 Compressors inverter minimum voltage 2
Cbg01 L2 Compressors inverter maximum voltage 0
Cbg01 L2 Compressors inverter nominal frequency 0 Hz
Cbg01 L2 Compressors inverter nominal power 25
Cbg02 L2 Compressors inverter rising time 0 s
Cbg02 L2 Compressors inverter falling time 30 s
************ -- --
L1 - FANS -- --
************ -- --
Dab01 L1 Fans regulation type 59 --
Dab01 L1 Fans control mode 0 PRESSURE
Dab02 L1 Minimum gas cooler setpoint 0
Dab02 L1 Maximum gas cooler setpoint 10
Dab03 L1 Gas cooler setpoint 0
Dab14 L1 Gas cooler neutral zone minimum complete activation time (neutral zone) 0 s
Dab14 L1 Gas cooler neutral zone maximum complete activation time (neutral zone) 0 s
Dab15 L1 Gas cooler neutral zone minimum complete deactivation time (neutral zone) 0 s
Dab15 L1 Gas cooler neutral zone maximum complete deactivation time (neutral zone) 60 s
Dad05 L1 Enable floating condensing setpoint compensation 0 °F
Dad06 L1 Floating condensing offset 0
Daf01 L1 Number of fans 15 --
Daf04 L1 Gas cooler refrigerant type 0 R22
Daf05 L1 Fans rotation type 200 --
Dag01 L1 Fans modulating device type 0 NONE
Dag02 L1 Fan inverter minimum voltage 0 V
Dag02 L1 Fan inverter maxiimum voltage 0 V
Dag02 L1 Fan inverter minimum activation 20 %
Dag02 L1 Fan inverter maxiimum activation 0 %
************ -- --
L2 - FANS -- --
************ -- --
Dbb01 L2 Fans regulation type 0 PROPORTIONAL BAND
Dbb01 L2 Fans control mode 0 PRESSURE
Dbb02 L2 Minimum Intercooler setpoint 0
Dbb02 L2 Maximum Intercooler setpoint 0
Dbb03 L2 Intercooler setpoint 0
Dbb14 L2 Intercooler neutral zone minimum complete activation time (neutral zone) 10 s
Dbb14 L2 Intercooler neutral zone maximum complete activation time (neutral zone) 0 s
Dbb15 L2 Intercooler neutral zone minimum complete deactivation time (neutral zone) 30 s
Dbb15 L2 Intercooler neutral zone maximum complete deactivation time (neutral zone) 4 s
Dbf01 L2 Number of fans 0 --
Dbf04 L1 Intercooler refrigerant type 0 R22
Dbf05 L2 Fans rotation type 10 --
Dbg01 L2 Fans modulating device type 4 --
Dbg02 L2 Fan inverter minimum voltage 0 V
Dbg02 L2 Fan inverter maxiimum voltage 0 V
Dbg02 L2 Fan inverter minimum activation 1 %
Dbg02 L2 Fan inverter maxiimum activation 0 %
************ -- --
TRANSCRITICAL -- --
************ -- --
Eib01 L1 Enable HPV control 0 NO
Eib05 L1 HPV valve regulation: pressure P100 0
Eib05 L1 HPV valve regulation: maximum pressure 0
Eib05 L1 HPV valve regulation: critical pressure 0
Eib05 L1 HPV valve regulation: temperature T12 0
Eib05 L1 HPV valve regulation: temperature T23 0
Eib05 L1 HPV valve regulation: temperature Tmin 0
Eib06 L1 HPV valve regulation: temperature T100 10
Eib06 L1 HPV valve regulation: delta subcooling correspondant to T23 0
Eib06 L1 HPV valve regulation: coefficient (m1) 0
Eib07 L1 HPV valve regulation: proportional gain 0 %/10psig
Eib07 L1 HPV valve regulation: integral time 0 s
Eib28 L1 HPV valve maximum safety setpoint 0
Eib28 L1 HPV valve minimum setpoint 0
Eib11 L1 HPV valve regulation: delta temperature on external temperature with gas cooler probe in alarm 0
Eib12 L1 Enable HPV safeties on receiver pressure 50 --
Eib18 L1 Enable RPRV control 0 NO
Eib22 L1 RPRV valve regulation: setpoint 0
Eib22 L1 RPRV valve regulation: proportional gain 0 %/10psig
Eib22 L1 RPRV valve regulation: integral time 0 s
Eic01 Enable HPV control on EVD 0 NO
Eic01 Enable RPRV control on EVD 0 NO
Eic01 EVD network address 0 --
Eic01 HPV/RPRV valve routing 4 --
Eic02 HPV valve type 0 CUSTOM
Eic02 RPRV valve type 0 CUSTOM
Eic03 HPV: EEV minimum steps custom 0 stp
Eic03 HPV: EEV maximum steps custom 0 stp
Eic03 HPV: EEV full close steps custom 3 stp
Eic03 HPV: EEV move rate custom 0 stp/s
Eic03 HPV: EEV move current custom 0 mA
Eic03 HPV: EEV holding current custom 0 mA
Eic04 HPV: move duty cycle custom 30 %
Eic04 HPV: EEV fast closing move rate custom 0 --
Eic05 RPRV: EEV minimum steps custom 0 stp
Eic05 RPRV: EEV maximum steps custom 0 stp
Eic05 RPRV: EEV full close steps custom 0 stp
Eic05 RPRV: EEV move rate custom 0 stp/s
Eic05 RPRV: EEV move current custom 0 mA
Eic05 RPRV: EEV holding current custom 0 mA
Eic06 RPRV: move duty cycle custom 0 %
Eic06 RPRV: EEV fast closing move rate custom 0 --
Eic22 Enable HPV backup function 0 NO
Eic22 Enable RPRV backup function 0 NO