Daikin LRMEQ5AY1E [10/156] Air cooled refrigeration condensing unit 9

Daikin LRLEQ12AY1E [10/156] Air cooled refrigeration condensing unit 9
SiENBE28-901 Standard Specification
Air Cooled Refrigeration Condensing Unit 9
Notes:
H1 [ ] shows the anti-corrosion treatment type.
H2 Rated conditions of the refrigeration equipment :
Saturated temperature equivalent to suction pressure: -10°C
Outdoor air: 32°C, Suction SH: 10°C
H3 Measurement place: Front: 1m, Height: 1.5m
4 The minimum connection load with inside unit: 2.0kW
Model 1
LRMEQ15AY1
[LRMEQ15AY1E]
LRMEQ20AY1
[LRMEQ20AY1E]
Power Supply 3 phase 50Hz 380-415V
Capacity 2 kW 32.2 37.0
Range of Suction Pressure Equivalent
Saturation Temperature
°C -20~+10
Range of Outdoor Temperature °C -15~+43
Casing Color Ivory white (5Y7.5/1) [Light camel (2.5Y6.5/1.5)]
Dimensions: (H×W×D) mm 1680×1240×765
Heat Exchanger Cross fin coil
Compressor
Type Hermetically sealed scroll type
Piston Displacement m
3
/h 30.00 35.80
Number of Revolutions r.p.m 5640, 2900 6960, 2900
Motor Output × Number of Units
kW 2.8+3.6+3.6 3.4+3.6+3.6
Starting Method Direct-on-line (Inverter system)
Fan
Type Propeller fan
Motor Output kW 0.75×2
Air Flow Rate
m
3
/min
230 240
Drive Direct drive
Connecting
Pipes
Liquid Pipe φ12.7 C1220T (Brazing connection)
Gas Pipe φ31.8 C1220T (Brazing connection)
Receiver Volume 12.1
Mass kg 355
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Overcurrent Relay,
Inverter Overload Protector, Fusible Plug
Capacity Control % 10~100 9~100
Refrigerant
Refrigerant Name R410A
Charge Volume kg 11.5
Refrigerant
Oil
Refrigerant Oil Name DAPHNE FVC68D
Charge Volume L 1.7+2.1+2.1+4.0
Operating Sound 3dBA62 63
Standard Accessories Installation Manual, Operation Manual, Connection Pipes, Clamps