068
MEDIUM STATIC PRESSURE DUCT
INVERTER
Slim & Compact design
Specifications
In the case of bottom return air connection, not only does
the indoor unit design allow for installation in a narrow
ceiling space of up to 270mm, Further space savings have
been achieved by mounting the electrical control box
internally inside the chassis.
1,135mm
1,200mm
270mm
Control box is now included as
part of the main chassis
One touch operating and easy to install
long life filter (Optional Parts)
(24)
Single
phase
(30/36/45)
For ARGG30/36LMLA-A
Wired R.C.
For ARGG24LMTA For ARGG45LMLA-A
Model : ARGG24LMTA / ARGG30LMLA-A / ARGG36LMLA-A / ARGG45LMLA-A
Capacity
EER
COP
Running Current
Moisture Removal
Airflow Rate (High)
Sound Pressure
Net Dimension H
x
W
x
D
Net Weight
Piping Connections (Small / Large)
Max Height Difference
Operation Range
Cooling
Heating
Drain Pipe Diameter (I.D./O.D.)
Max Pipe Length (Pre-Charge)
Refrigerant
Heating
Cooling/HeatingInput Power
Power Source
Cooling
Cooling
Indoor
Outdoor
Indoor (High)
Outdoor
Heating
Cooling/Heating
Indoor
Outdoor
°CDB
mm
m
kg(lbs)
mm
kW
kg(lbs)
A
W/W
m
3
/h
I/h
dB(A)
mm
V/ Ø/Hz
kW
BTU/h
kW
BTU/h
Model No.
Indoor unit
Outdoor unit
230/1/50
6.80
23,200
8.00
27,300
2.21/2.26
3.08
3.54
9.7/9.9
2.5
31
52
1,100
2,470
270x1,135x700
38.0(84)
578x790x315
44.0(97)
6.35/15.88
36.0/38.0
30(15)
20
-10 to 46
-15 to 24
R410A
230/1/50
8.50
29,000
10.00
34,100
2.65/2.68
3.21
3.73
11.6/11.7
2.5
39
53
2,100
3,600
270x1,135x700
40.0(88)
830x900x330
61.0(135)
9.52/15.88
36.0/38.0
50(20)
30
-15 to 46
-15 to 24
R410A
230/1/50
9.40
32,100
11.20
38,200
2.93/3.1
3.18
3.61
13.0/13.6
3.0
39
54
2,100
3,800
270x1,135x700
40.0(88)
830x900x330
61.0(135)
9.52/15.88
36.0/38.0
50(20)
30
-15 to 46
-15 to 24
R410A
230/1/50
12.10
41,300
13.30
45,400
3.77/3.68
3.21
3.61
16.5/16.1
4.0
42
55
2,100
6,750
270x1,135x700
40.0(88)
1290×900×330
88.0(194)
9.52/15.88
36.0/38.0
50(20)
30
-15 to 46
-15 to 24
R410A
ARGG24LMTA
AOGG24LALA
ARGG30LMLA-A
AOGG30LBTA-A
ARGG36LMLA-A
AOGG36LBTA-A
ARGG45LMLA-A
AOGG45LBTA-A
069
SPLIT / INVERTER
Low ambient operation
Dimensions Models: (Unit : mm)
Optional parts
Wired Remote Controller:
Simple Remote Controller:
Flange (Round):
Flange (Square):
Long Life Filter:
Remote Sensor Unit:
External Connect Kit:
External Control Set:
Drain Pump Unit:
IR Receiver Kit:
UTY-RNNGM
UTY-RSNGM
UTD-RF204
UTD-SF045T
UTD-LF25NA
UTY-XSZX
UTY-XWZXZ2
UTY-XWZXZ3
UTD-ECS5A
UTZ-PX1NBA
UTY-LRHGM
Easy maintenance
See below for the case of rear suction type
Structural improvement is attained by making the bottom panel two pieces, front
and rear. The internal fan casing is also manufactured in two pieces, namely
upper and lower. The maintenance of the motor and fan can be easily carried out
by removing the rear panel and the lower part of the casing while leaving the
main chassis installed.
Two-direction drain piping
1.Control box
2.Fan casing
3.Fan
4.Motor
Previous model
2
4
1
3
Large bottom
panel: 1 piece
New model
1
4
3
2
Bottom panel: 2 pieces
Two-direction drain piping
Duct indoor unit
Refrigerant piping flare connection (Liquid)
Refrigerant piping flare connection (Gas)
Drain piping connection
2
1
3
Rear view
Top view
Side view (R)
Side view (L)
Front view
240
270
107
1015
1135
173
161
447(Bolt pitch)
1177(Bolt pitch)
Outlet
270
32
ø200
(knock
out hole)
240
121
P.C.D. ø225
114
66
32
1
3
3
2
168
281
240
700
138
138
264 264 264
ø205 hole
82
75
50
40
30
20
10
0
-10
-15°C
Cooling
24°C
Heating
46°C
-15°C
-10°C
(24 type only)
Easy installation
Main work settings can be done easily
from the remote controller
at installation
Setting by wired remote controller
Conventional type
1
2
3
O
F
F
SW1
Setting by DIP switch inside control box
Main work settings
•High ceiling setting
•Auto restart
•Temperature adjustment when cooling / heating
ARGG24LMTA / ARGG30LMLA-A / ARGG36LMLA-A / ARGG45LMLA-A