General-Fujitsu ARG60RUAK [12/24] Error display

General-Fujitsu AOG60RPAGT [12/24] Error display
ERROR DISPLAY
CAUTION
Supply power to the crankcase heater for at least
12 hours before the start of operation in winter.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button
simultaneously for 2 seconds or more to start the test run.
2. OUTDOOR UNIT LEDS
Heat & Cool model (reverse cycle) only
When a malfunction occurs in the
outdoor unit, the LEDs on the cir-
cuit board light to indicate the error.
Refer to the following table for the
description of each error according
to the LEDs.
(3) Press the set temperature buttons simultaneously for
5 seconds or more to stop the self-diagnosis.
SU
MO
TU
WE
TH FR
SA
Unit number
(usually 0)
Ex. Self-diagnosis
Error code
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication E:EE is displayed, follow the follow-
ing items to perform the self-diagnosis. E:EE indicates an error
has occurred.
1. REMOTE CONTROLLER DISPLAY
1) Stop the air conditioner operation.
2) Press the set temperature buttons simultaneously for
5 seconds or more to start the self-diagnosis.
Refer to the following tables for the description of each error
code.
Test run display
Error code Error contents
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor short-
circuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
09
0A
0b
0c
0d
0E
0F
11
12
13
14
LED layout
Error code Error contents
Communication error
(indoor unit
remote controller)
Communication error
(indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor
open
Indoor heat exchanger temperature sensor
short-circuited
Outdoor heat exchanger temperature
sensor open
Outdoor heat exchanger temperature
sensor short-circuited
Power source connection error
00
01
02
03
04
05
06
07
08
S ignal abnormal
Indoor unit abnorm al
Discharge pipe
tem perature abnorm al
Outdoor heat ex changer
tem perature abnorm al
Outdoor temperature
abnorm al
Power sorce connection
error
E E PR OM abnorm al
Outdoor high pres s ure
abnorm al
Discharge pipe
tem perature abnorm al
E rror contents LED1 LED2 LE D3 LE D4 LED5 LED6
: 0.5s ON /0.5s OFF (flash) : OFF
: 0.1s ON /0.1s OFF (flash) : Indefinite
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pres-
sure abnormal, the LED lamp lights continuously for 24 hours, as
long as the power is not turned off.
2004.06.23 11
LED3
LED2
LED1
LED6
LED5
LED4