Haier AC182ACERA [340/408] Electric control functions

Haier AD482ANEAA [340/408] Electric control functions
1.8.9.1 Compulsory cooling operation
The unit enter compulsory cooling operation, as follow:
Compressor
startup
Current, discharging
protection and failure
treatment
Operation
before the base
open angle
3 minutes later after compressor is
running
Manual adjustment
normal normal normal 1: fixed base open angle 200- pace
2: fixed running frequency 60HZ(E)
3: fixed outdoor motor speed:
class-7
1: angle adjusted by hand
2:frequency adjusted by hand
3: fan speed adjusted by
hand
1.8.9.2 Compulsory heating operation
The unit enter compulsory heating operation, as follow:
Compressor
startup
Current, discharging
protection and failure
treatment
Operation
before the base
open angle
3 minutes later after compressor is
running
Manual adjustment
normal normal normal 1: fixed base open angle 200- pace
2: fixed running frequency 50HZ(E)
3: fixed outdoor motor speed: class-7
4. FQY is not limited by ambient temp.
1: angle adjusted by hand
2:frequency adjusted by hand
3: fan speed adjusted by
hand
1.8.10 High pressure switch
3 minutes later after compressor starts up, the system will check the pipe pressure. If the pipe pressure is
over high and high pressure switch acts for over 30 seconds, the compressor and outdoor motor will stop, 3
minutes later, the unit will resume. If in 60 minutes the unit stops for 3 times because of overhigh pressure, the
system will alarm, then compressor will not start up again; when being electrified after being powered off, the
protection will be cancelled.
1.8.11 Low pressure switch
When compressor works, if low pressure switch acts for 60 seconds contineously, the unti will alarm.
When compressor stops, if low pressure switch acts for 30 seconds contineously, the unti will alarm.
When compressor starts up, in 3 minutes, low pressure switch will be shielded.
In 6 minutes after defrosting is over, low pressure switch will be shielded.
1.8.12 Failure code and troubleshooting
z Alarm lamp is off when no failure, flash when failure occurs, the different flash time means different
failure.
Ensure that alarm indicating time is over 2 minutes and 50 seconds.
1˅Indoor pipe temp. is abnormal, outdoor default cooling temp. : 5ć, heating temp.: 40ć. The above
temperatures are normal.
2˅In defrosting, and in 3 minutes after defrosting is over, if sensor is abnormal, there will not alarm.
3˅Outdoor defrosting temp. sensor: when ambient temp. is below -5ć, detect after having start for 3 minutes.
Electric control functions
-323-