Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R410A is higher than that of the units for
use with R22, use pipes with at least the radial thickness specified in the chart below.
(Pipes with a radial thickness of 0.7mm or less may not be used.)
* Although it was possible to use type-O for pipes with a size of up to 19.05(3/4") with
conventional refrigerants, use type-1/2H pipes for units that use R410A.(Type-O pipes may
be used if the pipe size is
19.05 and the radial thickness is 1.2t.)
* The table shows the standards in Japan .using this table as a reference,choose pipes that
meet the local standards.
The flare machining dimensions for units that use R410A is larger than those for units that
use R22 in order to increase air tightness.
If a clutch type flare tool is used to machine flares on units that use R410A, make the
protruding part of the pipe between 1.0 and 1.5mm .Copper pipe gauge for adjusting the
length of pipe protrusion is useful.
Read Before Installation
10
<Piping Materials/Radial Thickness>
<Flare Machining(type-O and OL only)>
Flare Machining Dimension(mm)
External dimension
of pipes
Size
Dimension A
R410A
R22
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
9.1
13.2
16.6
19.7
24.0
9.0
13.0
16.2
19.4
23.3
<Flare Nut>
Type-2 flare nuts instead of type-1 s are used to increase the strength. The size of some of
the flare nuts have also been changed.
Flare nut dimension(mm)
External dimension
of pipes
Size
Dimension B
R410A(Type2)
R22(Type1)
6.35
9.52
12.7
15.88
19.05
1/4"
3/8"
1/2"
5/8"
3/4"
17.0
22.0
26.0
29.0
36.0
17.0
22.0
24.0
27.0
36.0
Size(mm) Radial Thickness(mm)Size(inch) Type
Type-O pipes
Type-1/2H or Hpipes
6.35
9.52
12.7
15.88
1/4''
3/8''
1/2''
5/8''
0.8t
0.8t
0.8t
1.0t
19.05 3/4''
1.0t
Содержание
- Dc inverter 1
- Installation instructions 1
- Outdoor unit 1
- Room air conditioner 1
- Name of parts 3
- Carefully read the following information in order to operate the air conditioner correctly 4
- Instructions 4
- Safety cautions 4
- Symbols used in the illustrations 4
- Warning 4
- Warning caution 4
- Safety cautions 5
- Warning 5
- Have the unit professionally installed 6
- Safety cautions 6
- Warning 6
- Caution 7
- Precautions for handling units for use with r410a 7
- Safety cautions 7
- Warning 7
- Before installing the unit 8
- Caution 8
- Safety cautions 8
- Warning 8
- Before installing relocating the unit or performing electric work 9
- Before the test run 9
- Caution 9
- Do not operate switches with wet hands to avoid electric 9
- Ground the unit 9
- Safety cautions 9
- Caution 10
- Items to be checked 10
- Necessary tools and materials 10
- Read before installation 10
- Piping materials 11
- Read before installation 11
- Tool and materials that must not used with r410a 11
- Tools and materials that are used with r22 or r407c that can also be used with r410a 11
- Tools and materials that may be used with r410 with some restrictions 11
- Tools for r410a must be handled with special care keep moisture and dust from entering the cycle 11
- Read before installation 12
- Airtightness test 13
- Items to be strictly observed 13
- Read before installation 13
- Reasons 13
- Vacuuming 13
- Characteristics of the conventional and the new refrigerants 14
- Charging refrigerant 14
- Read before installation 14
- Reasons 14
- Remedies to be taken in case of a refrigerant leak 14
- Accessories 15
- Installation procedure 15
- Selection of the place of installation 15
- Anchor bolt 16
- Au122aeera 16
- Au182afera 16
- Concrete foundation 16
- Installation of outdoor unit 16
- Installation procedure 16
- Au242agera 17
- Au282ahera au362ahera au36nahera 17
- Installation of outdoor unit 17
- Installation procedure 17
- Installation of outdoor unit 18
- Installation procedure 18
- Refrigerant piping 18
- 2 piping size 19
- 3 limitations for one way piping length and vertical height difference 19
- 4 piping connection 19
- Installation procedure 19
- Refrigerant piping 19
- Air discharging method 20
- Check if the pressure drops 20
- Installation procedure 20
- Charging amount of refrigerant 21
- Installation procedure 21
- Piping method to use wacuum pump e g au182afera 21
- Refrigerant piping 21
- Electric wiring 22
- Installation procedure 22
- Caution 23
- Installation procedure 23
- Test run 23
- Warning 23
- Electric wiring 24
- Installation procedure 24
- Trouble display 24
Похожие устройства
- Haier AU422AIERA Инструкция по монтажу
- Haier AU42NAIERA Инструкция по монтажу
- Haier AU522AIERA Инструкция по монтажу
- Haier AU52NAIERA Инструкция по монтажу
- Haier AC422AFERA Инструкция по эксплуатации
- Haier AC522AFERA Инструкция по эксплуатации
- Haier AU142AAERA Инструкция по монтажу
- Haier AD09LS1ERA Руководство по эксплуатации
- Haier AD09LS1ERA Сервис мануал
- Haier AD12LS1ERA Руководство по эксплуатации
- Haier AD12LS1ERA Сервис мануал
- Haier AD18LS1ERA Руководство по эксплуатации
- Haier AD24LS1ERA Руководство по эксплуатации
- Haier AD18LS1ERA Сервис мануал
- Haier AC18CS1ERA(S) Сервис мануал
- Haier AC24CS1ERA(S) Сервис мануал
- Haier 3U19FS1ERA Сервис мануал
- Haier 4U25HS1ERA Сервис мануал
- Haier 4U25HS1ERA Инструкция по монтажу
- Haier 4U30HS1ERA Сервис мануал