Haier 2HUM18HC03/R2(DB) [12/16] Caution
![Haier 2HUM18HC03/R2(DB) [12/16] Caution](/views2/1814524/page12/bgc.png)
2U14CS1ERA
2U18FS1ERA
1.
Tobend a pipe,givetheroundnessaslargeaspossiblenottocrushthepipe,
ƽ
andthebendingradiusshouldbe30to40
mm or longer.
Connecting the pipe of gas side first makes working easier.
ƽ
TheconnectionpipeisspecializedforR410A.ƽ
Half union
Flare nut
Torque wrench
CAUTION:
Be careful that matters, such as wastes of sand
s,water
, etc. shall not enter the pipe.
Spanner
Forced fastening without careful centering may
damagethethreadsandcause a leakageofgas.
Pipe Diameter(ǿ) Fastening torque
Liquid side6.35mm(1/4") 18N.m
Liquid/Gas side9.52mm(3/8") 42 N.m
Gasside12.7mm(1/2") 55N.m
Gasside15.88mm(5/8") 60N.m
Connection of pipes
2.
In case the elevation B is more than 5m,
oil trap shoud be installed every 5~7m
Max. Length:
B1
max
=20m B2
max
=20m
Max.Elevation:
A1
max
=15m
A2
max
=15m
In case the pipe total length (B1+B2) is more than
20m, the refrigerant should be charged, according
to 20 g/m.
B
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
Outdoor unit
Indoor unit
B1
Indoor unit
B2
Outdoor unit
Indoor unit
Oil trap
A3
A3
max
=15m
(B1+B2)
max
=30m
Outdoor unit
Indoor unit
A1
B1
Indoor unit
A2
B2
CAUTION
Indoor unit
Becarefulthatmatters,suchaswastesofsands,etc.shallnotenterthepipe.
The standard pipe length of each indoor unit is 5m. If total pipe length is over
20m, the function of the unit will be affected, charge more refrigerant is needed,
according to 20 g/m. But the charge of refrigerant must
be conducted by profes-
sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using a vacuum pump,then
charge additional refrigerant.
10
Содержание
- Contents 1
- Hum14hc03 r2 db 1
- Hum18hc03 r2 db 1
- Installation manual room air conditioner 1
- U14cs1era 1
- U18fs1era 1
- European regulations conformity for the models 2
- Haier industrial park no haier road qingdao p r china 2
- Important information rega rding the refrigerant used 2
- Air inlet 3
- Air outlet 3
- Compressor inside of unit 3
- Drain hose 3
- Indoor outdoor unit installation drawings 3
- Please be subject to the actual product purchased the above indoor and outdoor units picture is just for your reference 3
- Warning caution 4
- Cushion rubber 11
- Installation dimension unit mm 11
- Caution 12
- Each indoor unit musts to be vacuumed according to the above steps 14
- Enter into the cooling circulation system otherwise there will be abnormal high pressure in the system to make it crack and lead to personal injuries 14
- If the refrigerant of the air conditioner leaks it is necessary to discharge all the 14
- Refrigerant vacuumize first then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate please do not let other cooling medium except specified one r410a or air 14
- Outdoor unit 16
Похожие устройства
- Haier 2U18FS1ERA Инструкция по эксплуатации
- Haier 2U18FS1ERA Сервис мануал
- Haier 2U14CS1ERA Сервис мануал
- Haier 2U14CS1ERA Инструкция по эксплуатации
- Haier 2HUM14HC03/R2(DB) Инструкция по эксплуатации
- Haier AS07GS2ERA Инструкция по эксплуатации
- Haier AS07GS2ERA Сервис мануал
- Haier AS09GS2ERA Руководство по эксплуатации
- Trusty TYI-80/16SLN Список запчастей
- Trusty TYI-80/16SLN Взрыв_схема
- Trusty TYI-80/16SLN Инструкция по эксплуатации
- Trusty TSN-9040H Инструкция по эксплуатации
- Trusty TSN-9040H Взрыв_схема
- Haier AS18GS2ERA Руководство по эксплуатации
- Trusty TSN-9240H Взрыв_схема
- Trusty TSN-9240H Инструкция по эксплуатации
- Trusty TSN-16851 Взрыв_схема
- Trusty TSN-16851 Инструкция по эксплуатации
- Trusty TYI-9225 Список запчастей
- Trusty TYI-9225 Взрыв_схема