Haier AV32NMVERA Инструкция по монтажу онлайн [368/531] 616697

Haier AV26NMVERA Инструкция по монтажу онлайн [368/531] 616694
TC PI TC PI TC PI TC PI TC PI TC PI
DB WB
KW KW KW KW KW KW KW KW KW KW KW KW
AV40NMVERA heating mode
capacity
factor
outdoor temp.
indoor temp. (DB)
16.0 18.0 20.0 21.0 22.0 24.0
15.0 13.7 85.6 18.4 80.6 17.3 75.9 16.3 73.4 15.8 71.1 15.3 66.1 14.4
19.0 14.2 85.6 17.9 80.6 16.5 75.9 15.8 73.4 15.3 71.1 14.8 66.1 13.7
21.0 15.0 85.6 17.1 80.6 16.0 75.9 15.1 73.4 14.8 71.1 14.3 66.1 13.2
-14.7 -15.0 71.3 30.4 67.2 28.6 63.3 26.7 61.1 25.7 59.1 24.8 55.0 23.0
-12.6 -13.0 71.3 28.6 67.2 26.7 63.3 24.9 61.1 24.0 59.1 23.2 55.0 21.5
-10.5 -11.0 71.3 26.7 67.2 25.0 63.3 23.4 61.1 22.6 59.1 21.8 55.0 20.2
-9.5 -10.0 71.3 25.8 67.2 24.2 63.3 22.7 61.1 21.9 59.1 21.2 55.0 19.7
-8.5 -9.1 71.3 25.1 67.2 23.6 63.3 22.1 61.1 21.3 59.1 20.6 55.0 19.2
-7.0 -7.6 71.3 24.1 67.2 22.6 63.3 21.2 61.1 20.5 59.1 19.8 55.0 18.4
-5.0 -5.6 71.3 22.8 67.2 21.5 63.3 20.1 61.1 19.5 59.1 18.8 55.0 17.5
-3.0 -3.7 71.3 21.7 67.2 20.5 63.3 19.2 61.1 18.6 59.1 18.0 55.0 16.8
0.0 -0.7 71.3 20.2 67.2 19.1 63.3 17.9 61.1 17.4 59.1 16.8 55.0 15.7
3.0 2.2 71.3 19.0 67.2 17.9 63.3 16.9 61.1 16.3 59.1 15.8 55.0 14.8
5.0 4.1 71.3 18.3 67.2 17.3 63.3 16.2 61.1 15.7 59.1 15.2 55.0 14.3
7.0 6.0 71.3 17.6 67.2 16.6 63.3 15.7 61.1 15.2 59.1 14.7 55.0 13.8
9.0 7.9 71.3 17.0 67.2 16.1 63.3 15.1 61.1 14.7 59.1 14.2 55.0 13.4
11.0 9.8 71.3 16.4 67.2 15.5 63.3 14.7 61.1 14.2 59.1 13.8 55.0 12.9
13.0 11.8 71.3 15.9 67.2 15.0 63.3 14.2 61.1 13.8 59.1 13.4 55.0 12.5
15.0 13.7 71.3 15.4 67.2 14.6 63.3 13.8 61.1 13.4 59.1 13.0 55.0 12.2
19.0 14.2 71.3 14.9 67.2 14.0 63.3 13.3 61.1 12.8 59.1 12.5 55.0 11.7
21.0 15.0 71.3 13.9 67.2 13.6 63.3 12.9 61.1 12.2 59.1 12.0 55.0 11.2
TC: total capacity; PI: power input