Haier AV36NMVERA [13/531] Branch pipe 40 l7 l13 l14

Haier AV10NMVERA [13/531] Branch pipe 40 l7 l13 l14
13
6.7 Long piping length and high drop
when the distance between outdoors is over 2m, the oil
trap must be set (upright projecting pipe, 200mm high)
outdoor3
outdoor2
over 200mm
over 200mm
below 2m
below 2m
L7+L14+L1340m
L1
L5
L14
L15
L13
L12
L11
L10
L9
L8
L7
L6
L2+L3
10m
L4
L3
L2
L1
10m
outdoor1
max. drop:5m
outdoor is lower, max. drop is 40m
max. drop:15m
outdoor is uppper,max. drop is 50m
Max. length Pipe in above figure
Single way total pipe length 300
L1+L2+ L3+ L4+ L5+ L6+ L7+L8+ L9+ L10+
L11+ L12+ L13+ L14+ L15
Single way max. pipe length 150 L1+L2+ L3+ L5+ L7+ L14+ L13
Max. pipe length after 1
st
branch pipe
40 L7+L13+L14
Main pipe actual length 90 L5
Height difference between
indoors
15 ————
Height difference between
outdoors
5 ————