8.9 Utilized tool comparison for MRVIII R22 and R410A
TOOL PURPO8E R22 R410A REA8ON
Knife Cut the pipe Ο Ο
Expander Enlarge the pipe Ο Χ For R410A, must enlarge the projecting pipe.
Spanner Fasten the are nut Ο Χ Standard torque of 1/2, 5/8 pipe is larger.
Flare tool Flare the pipe Ο Ο
Pipe bender Bend the pipe Ο Ο
Pressure gauge Used in leakage test Ο Χ Leakage test pressure is higher.
Welding torch Brazing the pipe Ο Ο
Gauge manifold Evacuation device Ο Χ
Different pressure from R22: max.: HP5.3Mpa
min.: 3.5Mpa.
Charging hose Charging refrigerant Ο Χ
Vacuum pump with
one-way stop valve
Evacuation device Ο Χ
Must ensure oil in vacuum pump can not ow
into the unit when pump stops.
Charging cylinder Charging refrigerant Ο Χ R410A can not be charged as gas state.
Electronic charging
scale
Charging refrigerant Ο Ο
Leakage detector Leakage detecting Ο Χ
Can not use freon detector (CFCs or
HCFCs), R410A excludes Cl. Use the
hydrogen detector (or R134a detector).
Note:
The pipes of R410A connection with the same diameter can not be welded with the ared joints. You must expand
the diameter of pipe joint, then weld the connecting pipe.