Haier AE182FCBKA [72/126] Commercial air conditione

Haier AB092FCBIA [72/126] Commercial air conditione
Commercial Air Conditioner Model: AU242FHBIA,
AU482FIBIA, AU48NFIBJA
control In heating mode, EEV will be adjusted due to the overheating value: SH= TS-TC
1. Adjust range: according to the compressor frequency, min open angle of EEV will be
different: high frequency, 120; med frequency, 110; low frequency, 90; the max open
angle: 470/350
2. Overheating modification: according to the discharging temperature, modify the
overheating value, when Td>100ć, overheating value will decrease 2 at the standard
overheating value; when Td İ 70 ć , overheating value will add 2 at the standard
overheating value
3
4-way
valve
secure
operation
1. Secure operation conditions of 4-way valve:
ƽ After the outdoor receives the heating signal from indoor unit, if the 4-way valve is
not electrified before the compressor starts up, the unit will enter the 4-way valve
secure operation.
ƽ After defrosting is over, the unit will enter the 4-way valve secure operation.
2. 4-way valve secure operation control:
ƽ In heating mode, After the outdoor receives the startup signal from indoor unit, the
compressor will start up, (fan motor shutoff, EEV close) and when the frequency rises up
to 50Hz for 10 seconds, 4-way valve will reverse (meanwhile, fan motor will enter the
target speed, EEV enters the open angle of soft startup) and the unit enters soft startup
period.
ƽ In defrosting, when the defrost condition is met, the compressor frequency will
decrease to 50Hz, 4-way valve will reverse (meanwhile, fan motor will enter the target
speed) and the unit enters soft startup period.
3. 4-way valve control in OFF state:
4-way valve will close after compressor stops for 30 minutes.
4
Defrosting
control
1. Enter condition: when compressor runs for 45 minutes in
all in heating mode, by checking TE and TA, if the below
conditions can be met for continuous 5 minutes, the unit
will enter defrosting operation: TEİChTAˉ¢, herein,
ƽC˖TA˘0ć, C=0.8; TAı0ć, C=0.6
ƽ¢˖set as 12˄L˅,10˄M˅,8˄H˅ according to the
actual condition. At the easily defrosting place, set as H; at
the not-easy-defrosting place, set as L; when out of factory,
set as M
ƽTemperature limitation: -15ćEİTEİ2ćE
1. Enter condition:
when compressor
runs for 45 minutes
in all in heating
mode, by checking
TE and TA, if the
below conditions can
be met for
continuous 5
minutes, the unit will
enter defrosting
operation:
ƽWhen Ta˘2ć, TA-TE
ı9ć for continuous 2
minutes; or Te ˘ -12 ć
for continuous 5 minutes;
ƽWhen Taı2ć, Te˘-5
ć for continuous 5
minutes;
-72-