11.1.3 Troubleshooting for inverter units
yes
yes
yes
replace PCB
Are high pressure and
low pressure normal?
Are they too low?
If the pipe is
blocked?
Unclog piping
Air conditioner is
running in bad
condition?
replace PCB
Does indoor fan motor work properly in
heating cycle? Does outdoor fan motor
work properly in cooling cycle?
no
no
yes
yes
Is filter or heat exchanger dirty?
cleaning
no
Is piping twisted or
deformed?
yes
repair or replace
no
Measure equalized pressure and
running pressure to see if the
system is overfed or starved. Is
there a leak? Is capillary tube
clogged?
yes
Conduct leak test.
Evacuate and recharge
Note: This protection feature is not available with all models. In the event that compressor is on and off frequently for no
reason, check if the compressor is provided with discharging temperature protection. The protection is activated when
temperature is higher than 120° C and restored when lower than 100° C.
check fan motor and capacitor
Refrigerant charge is needed
Are stop valves in suction pipe and
liquid pipe of outdoor unit open?
no
open valves
Is discharging temperature detected
by a thermometer too high?
no
Is discharging temperature
sensor in good condition?
no
no no
yes
yes
yes
yes
1) Compressor discharging temperature protection
replace discharging sensor
start
-295-