Kentatsu KFKD112H0EN1 [5/32] Specifications

Kentatsu KFKD140H0EN1 [5/32] Specifications
5
KFKD middle static pressure duct

3. Specifications
Model KFKD_H0EN1 20 30 38
Air flow
H/M/L
m
3
/h
340/255/170 510/385/255 680/510/340
H/M/L CFM 200/150/100 300/225/150 400/300/200
External Static pressure Pa
50
Cooling
Capacity
H/M/L kW 2/1.74/1.52 2.7/2.31/2.03 3.6/3.11/2.66
Water flow rate
H l/h 344 464 619
Water pressure
drop
H kPa 5 11 19
Heating
Capacity
H/M/L kW 3.2/2.75/2.37 4.3/3.74/3.23 5.4/4.64/4.05
Water pressure
drop
H kPa 4.2 9.5 15.5
Power supply
V/ph/Hz
220-240/1/50
Power input
50Pa H W 45 60 67
Sound
pressure
level
50Pa H/M/L dB(A) 41/37/31 41/37/32 42/39/33
Fan motor
Type Low noise 4-speed fan motor
Quantity
1
1
1
Fan
Type
Centrifugal, forward-curved Blades
Quantity
1
2
2
Coil
Row
2
Max. working pressure
MPa
1.6
Diameter
mm Φ9.52
Body
Dimensions W
×
H
×
D mm 757
×
241
×
506 812
×
241
×
506 912
×
241
×
506
Packing W
×
H
×
D mm 806
×
265
×
558 871
×
265
×
558 971
×
265
×
558
Net weight kg 16 18.5 20
Gross weight kg 18 21 22.5
Pipe
connection
Water inlet/outlet pipe
Inch
RC3/4
Drain pipe mm ODΦ24
Note:
1. H: high fan speed; M: medium fan speed; L: low fan speed
2. Cooling conditions: entering water 7
°
C, temperature rise 5
°
C, entering air temperature 27
°
C DB,19
°
CWB.
Heating conditions: entering water 50
°
C, enter air temperature 20
°
C, the same water flow as the cooling conditions.
3. Noise is tested in semi-anechoic test room.

Содержание