Panasonic CW-A90VE [6/21] Cooling

Panasonic CW-A90VE [6/21] Cooling
5 Air Conditioner Performance Evaluation
5.1. Cooling
Intake & Discharge Air
Temperature Difference
Current Drain Determination Remedy
8°C and over (14.4°F)
As specified.
Nothing wrong.
None.
8°C and over (14.4°F)
Higher than specified.
Nothing wrong, outdoor
temperature is too high, heat
radiation is not efficient.
Improve heat radiation.
Under 8°C (14.4°F)
Higher than specified.
Something is preventing heat
radiation.
Excessive amount of refrigerant.
Improve heat radiation.
Under 8°C (14.4°F)
Lower than specified.
Leakage of refrigerant or
refrigerant system is blocked.
Locate and repair leak.
Flush refrigeration cycle.
Under 8°C (14.4°F)
Higher than specified by
50%.
Compressor defect or
compressor capacitor defect.
Replace the compressor or
compressor capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
5.2. Heating
Intake & Discharge Air
Temperature Difference
Current Drain Determination Remedy
14°C and over (25.2°F)
As specified.
Nothing wrong.
None.
14°C and over (25.2°F)
Higher than specified.
Nothing wrong, outdoor
temperature is high.
Something is preventing heat
radiation at indoor heat
exchanger.
None.
Clean air filter.
Under 14°C (25.2°F)
Lower than specified.
Nothing wrong, outdoor
temperature is low.
Something is preventing heat
radiation at outdoor heat
exchanger.
Leakage of refrigerant.
Refrigerant system is blocked.
None.
Improve heat radiation at outdoor
heat exchanger.
Locate and repair leak.
Flush refrigeration cycle.
Under 14°C (25.2°F)
Higher than specified by
50%.
Compressor defect.
Compressor capacitor defect
Replace the compressor.
Replace the compressor
capacitor.
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
6 Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
Trouble Check Result Cause Remedy
Fan Motor and
Compressor won’t run.
Supply Voltage
Fuse Box or Circuit
Breaker.
Power cord or
Wiring Harness.
Temperature
Setting.
Less than 10% by
Rated.
Open Contacts.
Pulled loose or
Shorted.
Higher than room
temperature
Temporary or Permanent?
Customer Restarted unit
immediately without waiting
3 minutes.
Consult ELECTRICIAN, if
permanent.
WAIT FOR 3 MINUTES.
Repair Open Circuit.
Repair or Replace it.
Set it LOWER.
Fan Motor won’t run
(Compressor run).
Objects around
Fan.
RESISTANCE
between Wires.
Capacitor Fan
Motor.
Main Control
Switch.
Locked Fan.
Shorted / Open
circuit.
OHM Meter doesn’t
Deflect.
No contacts at
Position Shown.
Fan Hitting Cowling
Foreign Materials.
Frozen Bearings.
Shorted or Burned out.
Capacitor Defect.
Main Control Switch defect.
Adjust Fan position setting
screw.
Remove Foreign Materials.
Replace Fan Motor.
Replace Fan Motor.
Replace Capacitor Fan.
Replace Main Control
Switch.
6
CW-A90VE / CW-A120VE