Panasonic WH-SDF09C3E5 [110/146] 5 outdoor air temperature sensor abnormality f36

Panasonic WH-UD09CE5-A [110/146] 5 outdoor air temperature sensor abnormality f36
110
17.5.25. Outdoor Air Temperature Sensor Abnormality (F36)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used
to determine sensor error.
Malfunction Caused:
1. Faulty connector connection.
2. Faulty sensor.
3. Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.