VTS VENTUS PRO PVS 18x21 [18/34] Air filters
![VTS VENTUS PRO PVS 24x24 [18/34] Air filters](/views2/1893540/page18/bg12.png)
17 18
OIMM – VENTUS PRO
Panel lters and zigzag lters are normally tted within the unit prior to shipping.
Bag lters are normally shipped in closed carton boxes to avoid any collection of dust and loss of efciency
prior to commissioning. Each bag lter is housed within a special holding frame with necessary locking spring
to ensure proper sealing.
Automatic roll lters consist of basic frame dispensing unit for clean media, rewind unit for dirty media, drive
system, roll lter media and control system. Normally lter media and control system are supplied loose for
site installation. For assembly, lter media roll is mounted on the dispensing unit taken along the guide channel
through working section and locked to the rewind unit.
Differential pressure switch must be installed and connected to the control panel.
Absolute lters are shipped in sealed carton boxes. While assembly, special care must be taken to ensure that
each lter cell is properly sealed within the assembly frame with no possibility of air leakage.
Other types of lters such as active carbon lters, sand lters etc. are supplied with manufacturer’s instructions
along with the units.
Filters that are shipped separately in the unit should be assembled after cleaning the inner surface by operating
the fan. Before start-up, make sure that lters are properly installed.
All coils are leak tested and checked prior to assembly. Fins are checked for proper condition. However, they
must be checked once more and combed out if necessary, because they might be damaged during handling and
installation. Do not remove plastic covers from coil pipe connections until the unit is ready for piping connectors.
Connections should be checked according to the project and the leakage should be taken in to account. System
layout should take into consideration of possible coil withdrawal.
It is recommended that the water ow is shut off when the fan is switched off. To avoid the overheating of the
heating coil, the hot water pump and water / steam valves should only be opened during the operation of fan.
Supply air control: The supply air temperature of the coil at the suction side should be max. 40˚C, otherwise the
overheating danger will occur.
Check the concentration ratio of the antifreeze before the start-up of the cooling coil. It should be enough for the
claimed operating temperature range. It should be taken in to account that the increasing concentration ratio of
the antifreeze decreases the performance of the coil.
The minimum temperature of the chilled water should be +20C, at lower temperatures freezing danger will occur.
Antifreeze is a dangerous chemical. The safety regulations of the antifreeze manufacturer should be taken in to
account.
Direct expansion coils will be supplied with a refrigerant distributor suitable for brazed connections. Refrigerant
pipe work must include necessary shut off devices, dehydrators, solenoid valves, oil traps etc. Selection, sizing,
installation and setting of thermostatic expansion valve should be in accordance with the recommendation of
condensing unit manufacturer.
Steam coils: Special care should be taken for collection and disposal of condensate within the coils and to
prevent entry of the condensate in the main into the coil by trapping it independently on a coil bypass. Condensate
connections to the stream trap must be of the same size as the coil outlet.
AIR FILTERS
COIL HEAT EXCHANGERS
3.7.3
3.7.4
! Do not operate coils above the maximum temperature and pressure specied on the capacity
label.
! If not otherwise stated on the capacity label, maximum operating temperature and pressure:
• for water coils (type:1) : 90ºC, 10 bar,
• for water coils (type:2) : 150ºC, 15 bar,
• for steam coils: 160ºC, 6 bar
!
Содержание
- Ahu supplied in packages for assembly on site 5 2
- Ahu supplied in sections 5 2
- Ambient conditions for ahu installation warunki zewnętrzne do pracy instalacji urządzenia 5 2
- Conditions for ahu assembly carried out by vts authorized service 6 2
- Connections 9 2
- Contents 2
- Foundation assembly connection of unit related systems 5 2
- General information and safety instructions 3 2
- Installation 7 2
- Maintenance 24 2
- Safety 19 2
- Setting up of components 17 2
- Start up 22 2
- Transport and storage 4 2
- Troubleshooting 31 2
- General information and safety instructions 3
- General information and safety instructions transport and storage 4
- Typical lifting equipment 4
- Foundation assembly connection of unit related systems 5
- Assembly completion 6
- Assembly site 6
- Conditions for ahu assembly carried out by vts authorized service 6
- Foundation assembly connection of unit related systems 6
- Preparation for assemmbling 6
- Installation 7
- Vts on site assembly does not include 7
- Fittings 8
- Ducted outle connections 10
- Ducted outlet conditions 10
- Rules ducted outlet connections 10
- Piping connections 11
- Rules ducted outlet connections with direction change 11
- Condensate drain lines 13
- Drainage u trap connection 13
- Electric connections 13
- Negative pressure 13
- Positive pressure 13
- Typical connections inverter powered ac motors 14
- Reset way 15
- Typical connections intermediate fan drive ac motors 15
- Motor terminal markings 16
- Thermal overload relay setting 16
- Air dampers 17
- Control system 17
- Setting up of components 17
- Air filters 18
- Coil heat exchangers 18
- Electric heater 19
- Humidifiers 19
- Safety 19
- Supply and return fans 19
- Observation of warning signs 20
- Staff training 20
- Use of the unit 20
- Air handling units are supplied with locked access doors as an option so unauthorized persons are not permitted to enter the sections which represent a danger the most important potential dangers for life and health are described below the units are manufactured in conformity with machinery normative 98 37 ec if the user thinks to take further measures to restrict every possible remaining danger he will be able to recognize them by the general description below 21
- Also lockout switches and suitable warnings should be used maintenance personnel should engage the lockout switch before starting any maintenance and repairs do not forget to protect against unlock by anybody else 21
- Centrifugal fans in air handling units are located inside a casing so accessibility to the fan is occasional or infrequent for this reason protective devices are offered as optional accessories only at specific user s request however as in case with other machinery involving moving parts common sense and caution will preserve personnel safety 21
- Drive guards safety guards should be used when drive systems are accessible by the personnel limit switch cuts off the power supply of the fan motor when door opens as the fan keeps on rotating do 21
- Fan inlet and outlet guards centrifugal fans in air handling units are usually connected directly to ductwork 21
- In addition to follow the manufacturer s installation instructions care must be taken to ensure compliance with federal state and local rules regulations and standards 21
- Not attempt to enter the unit within minimum 2minutes after opening the door 21
- Prevent of common dangers and risks 21
- Recommended safety practices 21
- The available optional guarding devices are 21
- This publication explains the proper use and installation of centrifugal fans in order to warn operating and maintenance personnel of the commonly recognized dangers associated with this equipment 21
- Which will prevent the contact with the internal moving parts in case there is an exposed inlet or outlet which could represent a danger suitable guards can be installed 21
- Start up 22
- The hidden danger 22
- Operations of fans 23
- After two week operation 24
- Maintenance 24
- After inspection and replacements if necessary proceed in accordance with operation instructions before running the unit again 25
- Fan sections 25
- Following must also be noted about maintenance works 25
- For detailed information about lubrication of bearings belt tension and alignment controls changing of pulleys see related sections in this manual 25
- Coil sections 26
- Filter sections 26
- After opening the service door the filters can be taken out by pulling aside 27
- Humidifier sections 27
- Humidifier should be cleaned regularly the period changes according to the operating conditions air specifications and water quality during periodic maintenance of humidifier checks mentioned in its own manual should be performed 27
- Prevent of common dangers and risks 27
- Sound attenuators 27
- Sound attenuators can be taken out from the service door by unscrewing the components from the top and bottom panels attenuators can be cleaned by vacuumed or compressed air 27
- Synthetic bag filter can be cleaned by vacuumed or compressed air besides can be washed with the sensitive detergent and warm water 27
- Belt tension and alignment control 28
- Change of pulleys 28
- Bearing inner diameter mm 29
- Bearings have to be controlled and cleaned regularly have to be lubricated adequately to prevent direct metallic contact between rolling elements to prevent wear and to project bearing surfaces against corrosion 29
- D bearing inner diameter mm 29
- Excess grease will cause the operating temperature to rise rapidly particularly when running at high speeds therefore only the bearing should be completely filled whilst the free space in the housing should be partly filled between 30 and 50 where bearings are to operate at very low speeds and must be well protected against corrosion it is advisable to completely fill the housing 29
- Fan speed 29
- If the fan works in particular conditions relubrication intervals have to be corrected concerning the temperature and surrounding factors according to the following formula 29
- Ks surrounding correction factor 29
- Kt temperature correction factor 29
- Lubrication of bearings 29
- N fan speed rpm 29
- Relubrication interval depends on the fan speed and bearing internal diameter and is calculated by the following formula 29
- T 10 x 14x106 n x d 4 x d 29
- T relubrication interval h 29
- Tc corrected relubrication interval 29
- Tc t x kt x ks 29
- Temperature correction factor kt takes into account the reduction of relubrication interval when bearing temperature raised over 70 º c 29
- The fans with higher shaft power are equipped with bearings with cast iron support the lubricant filled in a bearing gradually loses its lubricating properties during operation therefore it is necessary for grease to be replenished or renewed from time to time the grease used is always lithium soap type suitable for all temperatures within the operating range 29
- The fans with low shaft power are equipped with bearings in a rubber housing which absorbs a part of vibration when you change the bearing it is very important to change the rubber housing too these bearings don t need to be lubricated 29
- Relubrication procedures 30
- Replenishment 30
- Renewing the grease fill 31
- Troubleshooting 31
- Possible cause 32
- Troubleshooting 32
- Heating coil low heating 33
- Heating coil no heating 33
- High air flow 33
- Low air flow 33
- Possible cause 33
- Troubleshooting cont 33
- Cooling coil no cooling 34
- Electrical heater 34
- Electroni c steam humidifier low humidifying 34
- Electronic steam humidifier no humidifying 34
- Low heat 34
- No cooling 34
- Possible cause 34
- Troubleshooting cont 34
Похожие устройства
- VTS VENTUS PRO PVS 18x21 Инструкция по инсталляции
- VTS VENTUS PRO PVS 18x21 Брошюра
- VTS VENTUS PRO PVS 18x21 Сертификат
- VTS VENTUS PRO PVS 21x21 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 21x21 Инструкция по инсталляции
- VTS VENTUS PRO PVS 21x21 Брошюра
- VTS VENTUS PRO PVS 21x21 Сертификат
- VTS VENTUS PRO PVS 24x24 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 24x24 Инструкция по инсталляции
- VTS VENTUS PRO PVS 24x24 Брошюра
- VTS VENTUS PRO PVS 24x24 Сертификат
- VTS VENTUS PRO PVS 27x27 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 27x27 Инструкция по инсталляции
- VTS VENTUS PRO PVS 27x27 Брошюра
- VTS VENTUS PRO PVS 27x27 Сертификат
- VTS VENTUS PRO PVS 31x31 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 31x31 Инструкция по инсталляции
- VTS VENTUS PRO PVS 31x31 Брошюра
- VTS VENTUS PRO PVS 31x31 Сертификат
- VTS VENTUS PRO PVS 34x34 Инструкция по эксплуатации