VTS VENTUS PRO PVS 31x31 [32/34] Possible cause

VTS VENTUS PRO PVS 24x24 [32/34] Possible cause
31 32
OIMM – VENTUS PRO
TROUBLESHOOTING
PROBLEM SYMPTOMS
POSSIBLE CAUSE
OTHER CAUSES OR ACTION
NOISE
Impeller hits inlet ring
Damaged impeller Correct or change impeller
Damaged inlet ring Correct or change inlet ring
Impeller not centered on shaft Center the impeller
Shaft loose in bearing Tighten shaft
Impeller loose on shaft Tighten impeller
Noise from drive
system
Belts too loose Adjust belt tension
Belts too tight Adjust belt tension
Belts wrong section Install correct section belts
Belts worn Change belts
Belts oily or dirty Clean belts
Belts length different (multi-belt
drives)
Install correct belts.
Drive systems hits drive guard Check drive system and drive guard.
Fan, motor or motor base xing
bolts loose
Tighten bolts
Pulleys misaligned. Align pulleys
Variable speed pulleys not adjusted
so each groove has different
diameter.
Adjust each groove to same
diameter for required air ow
Fan shaft bent Correct or change shaft
Motor bearings damaged Change bearings
Noise from bearings
Loose on support Tighten bearings
Loose on shaft Tighten shaft
Bearings worn or damaged Change bearings
Bearings need lubrication Lubricate bearings
Foreign material inside bearing Clean bearings
Corrosion between shaft and
bearings
Clean corrosion, if the shaft worn
change shaft
High air velocity
Ductwork undersized for application
Check duct size and revise if
necessary
Fan size is too small for application
Change size of equipment, revise if
necessary
Coil with insufcient face area
Registers and/or grilles undersized
for application
Worn or damaged impeller Change impeller
Unbalanced impeller Balance impeller
Foreign material in fan housing or
inside the unit
Clean fan housing
Vibrating ductwork Stiffen ductwork
Vibrating casing parts Isolate vibrating parts properly
Vibrating parts not isolated from
building
Obstruction in dampers, registers,
grilles
Check and remove any obstructions
Leaks in casing and ductworks Seal leaks
Sharp elbows
Remove sharp elbows, install
elbows with proper radius and
turning vanes
Sudden expansion or reduction in
ductwork
Install expansion/reduction sections
with proper expansion/reduction
angles