VTS VENTUS PRO PVS 34x34 [31/34] Renewing the grease fill
![VTS VENTUS PRO PVS PO 120 AC [31/34] Renewing the grease fill](/views2/1893540/page31/bg1f.png)
31
OIMM – VENTUS PRO
When the end of the relubrication interval t, has been reached, the used grease in the bearing should be
completely removed and replaced by fresh grease. As stated before, under normal conditions, the free space
in the bearing should be completely lled and the free space in the housing lled to between 30 and 50 % with
fresh grease. Great care should be taken to see that contaminants are not introduced into the bearing or housing
when relubrication.
Before checking the fan system, it will be necessary to shut down the fan. During inspection, the unit must be
isolated electrically and all disconnected switches and other controls must be locked in the “off” position. Also,
a prominent “DO NOT START” sign should be placed on control panel.
To nd out the problem is an important step to correct it. By following the procedures outlined in this section,
cause of the problem should be found.
Procedure for troubleshooting:
• Look at the troubleshooting chart to nd the problem. Check probable causes.
• If the cause of the problem can not be found proceed through the “system checklist”
• If the problem still can not be solved, it is recommended to contact the “unit manufacturer”
System checklist
A systematic check of items listed below may identify the problem. See that:
a) impeller rotation is correct,
b) pulley are aligned,
c) belts are not loose or too tight,
d) belts and/or pulley are not worn,
e) ow surfaces of fan (impeller blades, housing and passages between inlets) are clean,
f) impeller and housing are not damaged,
g) coils, lters, ducts are clean.
h) fan outlet connections are correctly designed and installed,
i) variable inlet vanes are synchronised. If inlet vanes are not synchronised, there will be an unbalance ow
between inlets causing thrust on bearing and low performance, inlet vanes are correctly positioned for the
designed operating conditions,
j) there is no leak in the unit and ductwork. Some common leak sources are access doors, coil, duct joints,
fan outlet connections etc.
If the cause of the problem still can not be found, consult air handling unit manufacturer. Manufacturer may need
following information:
k) complete drawings including unit location, ductwork detail, model and size of the unit,
l) measured and design performance gures,
m) system design calculations,
n) measured fan performance gures such as fan static pressure, air volume, current drawn, fan speed, air
temperature and altitude etc.
RENEWING THE GREASE FILL
TROUBLESHOOTING
3.10.8.3
3.11
Содержание
- Ahu supplied in packages for assembly on site 5 2
- Ahu supplied in sections 5 2
- Ambient conditions for ahu installation warunki zewnętrzne do pracy instalacji urządzenia 5 2
- Conditions for ahu assembly carried out by vts authorized service 6 2
- Connections 9 2
- Contents 2
- Foundation assembly connection of unit related systems 5 2
- General information and safety instructions 3 2
- Installation 7 2
- Maintenance 24 2
- Safety 19 2
- Setting up of components 17 2
- Start up 22 2
- Transport and storage 4 2
- Troubleshooting 31 2
- General information and safety instructions 3
- General information and safety instructions transport and storage 4
- Typical lifting equipment 4
- Foundation assembly connection of unit related systems 5
- Assembly completion 6
- Assembly site 6
- Conditions for ahu assembly carried out by vts authorized service 6
- Foundation assembly connection of unit related systems 6
- Preparation for assemmbling 6
- Installation 7
- Vts on site assembly does not include 7
- Fittings 8
- Ducted outle connections 10
- Ducted outlet conditions 10
- Rules ducted outlet connections 10
- Piping connections 11
- Rules ducted outlet connections with direction change 11
- Condensate drain lines 13
- Drainage u trap connection 13
- Electric connections 13
- Negative pressure 13
- Positive pressure 13
- Typical connections inverter powered ac motors 14
- Reset way 15
- Typical connections intermediate fan drive ac motors 15
- Motor terminal markings 16
- Thermal overload relay setting 16
- Air dampers 17
- Control system 17
- Setting up of components 17
- Air filters 18
- Coil heat exchangers 18
- Electric heater 19
- Humidifiers 19
- Safety 19
- Supply and return fans 19
- Observation of warning signs 20
- Staff training 20
- Use of the unit 20
- Air handling units are supplied with locked access doors as an option so unauthorized persons are not permitted to enter the sections which represent a danger the most important potential dangers for life and health are described below the units are manufactured in conformity with machinery normative 98 37 ec if the user thinks to take further measures to restrict every possible remaining danger he will be able to recognize them by the general description below 21
- Also lockout switches and suitable warnings should be used maintenance personnel should engage the lockout switch before starting any maintenance and repairs do not forget to protect against unlock by anybody else 21
- Centrifugal fans in air handling units are located inside a casing so accessibility to the fan is occasional or infrequent for this reason protective devices are offered as optional accessories only at specific user s request however as in case with other machinery involving moving parts common sense and caution will preserve personnel safety 21
- Drive guards safety guards should be used when drive systems are accessible by the personnel limit switch cuts off the power supply of the fan motor when door opens as the fan keeps on rotating do 21
- Fan inlet and outlet guards centrifugal fans in air handling units are usually connected directly to ductwork 21
- In addition to follow the manufacturer s installation instructions care must be taken to ensure compliance with federal state and local rules regulations and standards 21
- Not attempt to enter the unit within minimum 2minutes after opening the door 21
- Prevent of common dangers and risks 21
- Recommended safety practices 21
- The available optional guarding devices are 21
- This publication explains the proper use and installation of centrifugal fans in order to warn operating and maintenance personnel of the commonly recognized dangers associated with this equipment 21
- Which will prevent the contact with the internal moving parts in case there is an exposed inlet or outlet which could represent a danger suitable guards can be installed 21
- Start up 22
- The hidden danger 22
- Operations of fans 23
- After two week operation 24
- Maintenance 24
- After inspection and replacements if necessary proceed in accordance with operation instructions before running the unit again 25
- Fan sections 25
- Following must also be noted about maintenance works 25
- For detailed information about lubrication of bearings belt tension and alignment controls changing of pulleys see related sections in this manual 25
- Coil sections 26
- Filter sections 26
- After opening the service door the filters can be taken out by pulling aside 27
- Humidifier sections 27
- Humidifier should be cleaned regularly the period changes according to the operating conditions air specifications and water quality during periodic maintenance of humidifier checks mentioned in its own manual should be performed 27
- Prevent of common dangers and risks 27
- Sound attenuators 27
- Sound attenuators can be taken out from the service door by unscrewing the components from the top and bottom panels attenuators can be cleaned by vacuumed or compressed air 27
- Synthetic bag filter can be cleaned by vacuumed or compressed air besides can be washed with the sensitive detergent and warm water 27
- Belt tension and alignment control 28
- Change of pulleys 28
- Bearing inner diameter mm 29
- Bearings have to be controlled and cleaned regularly have to be lubricated adequately to prevent direct metallic contact between rolling elements to prevent wear and to project bearing surfaces against corrosion 29
- D bearing inner diameter mm 29
- Excess grease will cause the operating temperature to rise rapidly particularly when running at high speeds therefore only the bearing should be completely filled whilst the free space in the housing should be partly filled between 30 and 50 where bearings are to operate at very low speeds and must be well protected against corrosion it is advisable to completely fill the housing 29
- Fan speed 29
- If the fan works in particular conditions relubrication intervals have to be corrected concerning the temperature and surrounding factors according to the following formula 29
- Ks surrounding correction factor 29
- Kt temperature correction factor 29
- Lubrication of bearings 29
- N fan speed rpm 29
- Relubrication interval depends on the fan speed and bearing internal diameter and is calculated by the following formula 29
- T 10 x 14x106 n x d 4 x d 29
- T relubrication interval h 29
- Tc corrected relubrication interval 29
- Tc t x kt x ks 29
- Temperature correction factor kt takes into account the reduction of relubrication interval when bearing temperature raised over 70 º c 29
- The fans with higher shaft power are equipped with bearings with cast iron support the lubricant filled in a bearing gradually loses its lubricating properties during operation therefore it is necessary for grease to be replenished or renewed from time to time the grease used is always lithium soap type suitable for all temperatures within the operating range 29
- The fans with low shaft power are equipped with bearings in a rubber housing which absorbs a part of vibration when you change the bearing it is very important to change the rubber housing too these bearings don t need to be lubricated 29
- Relubrication procedures 30
- Replenishment 30
- Renewing the grease fill 31
- Troubleshooting 31
- Possible cause 32
- Troubleshooting 32
- Heating coil low heating 33
- Heating coil no heating 33
- High air flow 33
- Low air flow 33
- Possible cause 33
- Troubleshooting cont 33
- Cooling coil no cooling 34
- Electrical heater 34
- Electroni c steam humidifier low humidifying 34
- Electronic steam humidifier no humidifying 34
- Low heat 34
- No cooling 34
- Possible cause 34
- Troubleshooting cont 34
Похожие устройства
- VTS VENTUS PRO PVS 34x34 Инструкция по инсталляции
- VTS VENTUS PRO PVS 34x34 Брошюра
- VTS VENTUS PRO PVS 34x34 Сертификат
- VTS VENTUS PRO PVS 37x37 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 37x37 Инструкция по инсталляции
- VTS VENTUS PRO PVS 37x37 Брошюра
- VTS VENTUS PRO PVS 37x37 Сертификат
- VTS VENTUS PRO PVS 21x40 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 21x40 Инструкция по инсталляции
- VTS VENTUS PRO PVS 21x40 Брошюра
- VTS VENTUS PRO PVS 21x40 Сертификат
- VTS VENTUS PRO PVS 21x43 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 21x43 Инструкция по инсталляции
- VTS VENTUS PRO PVS 21x43 Брошюра
- VTS VENTUS PRO PVS 21x43 Сертификат
- VTS VENTUS PRO PVS 24x46 Инструкция по эксплуатации
- VTS VENTUS PRO PVS 24x46 Инструкция по инсталляции
- VTS VENTUS PRO PVS 24x46 Брошюра
- VTS VENTUS PRO PVS 24x46 Сертификат
- VTS VENTUS PRO PVS PO 25 AC Инструкция по эксплуатации